background image

©

 All rights reserved. All trademarks are property of their respective owners.

 

 

1.

 

Ensure the UPS is turned off and disconnected from the main power. 

2.

 

Unscrew the front panel. 

3.

 

Push the front panel upward then pull out the front panel. 

4.

 

Remove the battery cover, disconnect battery cable, then remove the battery. (negative pole first) 

5.

 

Replace with the same type and quantity of battery. 

6.

 

Reinstall the battery cover and front panel. 

APP-A. Troubleshooting 

Troubleshooting  procedures  give  simple  instructions  in  determining  UPS  malfunctions.  Start  the 

troubleshooting procedure if you witness any alarm indication. 

Alarm 

 

The  UPS has an audible alarm. When  different situations  occurred, UPS will alert users with display 

and buzzer. 

Battery-mode (Slow alarm) 

During  battery  mode,  the  alarm  will  beep  every  2  seconds.  The  alarm  will  stop  when  UPS  return  to 

Line-mode. 

Battery-Low (Rapid alarm) 

During Battery-low (less than 30%), the UPS will beep every 0.5 seconds. The alarm will stop when UPS 

shutdown or returns to Line-mode. 

Overload (Constant alarm) 

When  UPS  operating  with  load  exceeded  its  maximum  capacity,  UPS  will  emit  a  continuous  alarm  to 

warn an  overload  condition. UPS will automatically turn  off  to protect  your  essential  load. Please consider 

remove or shutdown less-essential loads. 

Silencing Alarm 

Here is the instruction to mute the active alarm or future alarm notification: 

Note

:  During  battery-mode,  if  the  battery  is  low  on  power,  the  alarm  will  sound  regardless  of 

silent-mode enable/disable. 

If  troubleshooting  does  not  include  or  resolve  your  situation,  feel  free  to  contact  for  technical 

assistance. 

PROBLEM 

POSSIBLE CAUSE 

Solutions 

UPS can't operate 

switching on. 

No lights on, 

no warning sound 

Power source mistake or low 

battery power 

Check the main power connection 

If operating with battery power, 

ensure enough charging time for UPS 

Time of pressing the button is 

too short 

Press and hold the "ON" button for 

a longer duration 

Output short circuit or overload 

on UPS 

Turn off UPS and take off all load 

Check for any potential internal short circuit 

Then attempt to turn on UPS again 

Hardware failure 

Contact for technical assistance 

Battery out of order 

Replace battery or contact for technical 

assistance 

UPS always remain on 

battery-mode regardless 

of main power 

connection 

No power source input 

Check the main power source and cable 

Fuse melted or Circuit breaker 

tripped 

Reset the breaker or replace the fuse 

(spare fuse is in UPS inlet.)   

then restart the UPS 

The main voltage is out of the 

UPS input range 

UPS function normally, 

check your main power voltage 

Overload/Fault indicator 

lit or constant buzzer 

beeping 

UPS load exceed the capacity 

UPS overloading 

Remove or shut down the 

less essential load 

Battery mode duration 

below expectation 

Batteries aren't fully charged 

Batteries are worn out or faulted 

Ensure enough recharge time for UPS 

Run a self-test to check battery status 

Replace UPS battery if the problem remains 

The charger is out of order 

Contact for technical assistance 

Green mode enabled 

No-load or light load shutdown 

engaged 

Operation normal 

Turn off green mode to disable such function 

The battery fault 

indicator occurred 

Battery not connected 

Check the UPS batteries; 

make sure they are well connected 

Battery out of order or damaged 

Replace battery 

Summary of Contents for IMD-1025A

Page 1: ...ne Interactive 1025VA 3000VA IMD 1025A IMD 1025AP IMP 1025A IMP 1025AP IMD 1200A IMD 1200AP IMP 1200A IMP 1200AP IMD 1500A IMD 1500AP IMP 1500A IMP 1500AP IMD 2000A IMD 2000AP IMP 2000A IMP 2000AP USE...

Page 2: ...greater distance between the receiver and the equipment Ensure that your Equipment connects to an outlet on a separate circuit Contact a technician experienced with radio and TV or the dealer for tec...

Page 3: ...ceable parts inside Please refer all service to qualified service technicians CAUTION DO NOT dispose UPS and its batteries to fire the battery may explode CAUTION DO NOT attempt to open or mutilate th...

Page 4: ...ne Interactive UPS it is capable of providing clean and stable power to your critical system While the UPS regulates and filters power fluctuation it also keeps the battery charged for any emergency A...

Page 5: ...during Line Battery mode If applicable To avoid electrical hazards please turn off the internal external input breaker Then turn off any external battery breaker and wait till all fans completely shu...

Page 6: ...C to 25 C Protect the equipment from wet or damp areas and moist air To maintain the vitality of the batteries please recharges the UPS at least 8 hours every six months 6 3 Operation CAUTION Ensure t...

Page 7: ...situation feel free to contact for technical assistance PROBLEM POSSIBLE CAUSE Solutions UPS can t operate switching on No lights on no warning sound Power source mistake or low battery power Check th...

Page 8: ...Beep every 2 seconds Low Battery Beep every 0 5 second Environment Operating Humidity 0 90 RH at 0 40 C Non condensing Audible Noise Less than 40 dB IMD Series are same specification with IMP Series...

Reviews: