6 hours
3. Product Overview
Front View:
VI 1000 LED
VI 1500 / 2000 LED
Back View:
VI 1000 LED
VI 1500 / 2000 LED
4.
Installation and Initial Startup
NOTE:
Before installation, please inspect the unit. Be sure that nothing inside the package
is damaged.
1) Placement & Storage Conditions
Install the UPS in a protected area that is free of excessive dust and has adequate air flow.
Please place the UPS away from other units at least 20 cm to avoid interference. Do NOT
operate the UPS where the temperature exceeds 0-40° C and the humidity is over 0-90 %
RH.
2) Connect to Utility and Charge
Plug in the AC input cord to the wall outlet. For the best
results, we suggest charging the battery at least 6 hours
before initial use. The unit charges its battery while
connecting to the utility.
3) Connect the Loads
Plug in the loads to output receptacles on the rear panel of the UPS. Simply turn on the
power switch of UPS unit, and devices connected to the UPS will be protected by UPS unit.
4) Connect Modem/Phone/Network for Surge Protection (Only for the model
with RJ-45)
Connect a single modem/phone line into surge-protected “IN” outlet on the back panel of
the UPS unit. Connect from “OUT” outlet to the computer with phone line cable.
5) Connect USB Cable
To monitor the UPS status, such as unattended UPS shutdown and start-up, by using
bundled software, please connect the UPS and PC with USB cable included.
6) Turn On/Off the Unit
Turn on the UPS unit by pressing the power switch. Turn off the UPS unit by pressing again
the power switch.
5. Audible alarm from the UPS
•
When UPS switches from AC mode to Battery Mode to back up power supply:
sounding every 10 seconds
•
When battery is low: sounding every second
•
When UPS is overloaded: sounding every 0.5 second
•
When battery is faulty: sounding every 2 seconds
Other fault: Continuously sounding
6. Software Installation on your PC
1) Use the bundled CD and follow the on-screen instructions to install the software View
_Power.
2) After the software is successfully installed, the communication with UPS has been
established and an orange icon will appear in the system tray.
3) Double-click the icon to use the monitor (as above).
You can schedule UPS shutdown/start-up and monitor UPS status through PC.
Detail instructions please refer to the e-manual in the software.
Do not attach a power strip or surge suppressor to the UPS.
NEVER
connect a
laser printer
or
scanner
to the UPS unit,
because in-rush current
generated by motor’s devices
may cause the
damage of the unit.
X
Power switch
Y
AC mode indicator: green
lighting
Z
Battery mode indicator: yellow
lighting
[
Fault indicator: red lighting
\
UPS status indicator:
AC mode: green lighting
Battery mode: green flashing
]
AC mode: load level indicator
Battery mode: battery capacity
indicator
X
Output receptacles
Y
AC input
Z
Circuit breaker
[
Modem/phone/Network surge
protection
\
USB port
GB