PowerGuard Controller Test Procedure 

After following Set-Up Procedure, system must be tested to ensure Trip Speed was programmed correctly. Entering 
TEST Mode causes system to trip at ‘Input Speed’ from Set-Up Procedure – raising engine speed to actual ‘Trip 
Speed’ is unsafe and unnecessary. 

1.

 

With engine running at idle, enter TEST Mode: 

 

Hold 

 

SET 

 & 

 

TEST 

 

until both lights begin to flash and then press & release 

 

TEST

.

 

 

 

Pre-Set Controllers: Hold 

 

TEST 

 

for 3 seconds 

2.

 

Increase engine speed to ‘Input Speed.’ 

3.

 

Valve will close and red light will illuminate until 0 RPM is detected and 30 seconds elapses 

 

Pressing 

 

TEST 

 

will bypass 30 second timer 

4.

 

When red light extinguishes valve will be safe to re-open manually 

5.

 

If valve did not close, controller was not successfully programmed. Confirm installation and re-follow Set-Up 
Procedure. 

5

 

Additional Functions 

5.1

 

Factory Reset 

This function clears any existing programming and restores controller to its original factory condition. When 
performed, both lights will begin to flash alternatingly. To perform Factory Reset: 

 

Hold 

 

SET

 

 & 

 TEST 

 until both lights begin to flash and then press & hold 

 

SET

.

 

  

5.2

 

Manual Trip 

This function closes PowerHalt valve and causes engine (if running) to shut down. To perform Manual Trip: 

 