background image

www.powershield.com.au 

  18 

3-5. Parallel Operation 

1. Parallel system initial startup 

First of all, please make sure all of the UPSs are parallel models and have the same configuration. 
1)    Turn on each UPS to AC mode respectively (Refer to section 3-4(1)). Then, measure the output 

voltage of each UPS to check if the voltage difference between actual output and setting value is 

less than 1.5V (typical 1V) with multimeter. If the difference is more than 1.5V, please calibrate the 

voltage by configuring inverter voltage adjustment (Refer to Program 15, section 3-7) in LCD 

setting. If voltage difference remains more than 1.5V after calibration, please contact your local 

distributor or service center for help. 

2)  Calibrate the output voltage measurement by configuring output voltage calibration (Refer to 

Program 16, section 3-7) in LCD setting to make sure the error between real output voltage and 

detected value of UPS is less than 1V.   

3)  Turn off each UPS (Refer to section 3-4(7.)). Then, follow the wiring procedure in section 2-4.   
4)  Remove the cover of parallel share current cable port on the UPS, connect each UPS one by one 

with the parallel cable and share current cable, and then screw the cover back. 

5) 

  Turn on the parallel system in AC mode:

 

a)

 

Turn on the input breaker of each UPS. After all UPSs enter to bypass mode, measure the 

voltage between output L1 of each UPS and output L2 of each UPS. If these two voltage 

differences are all less than 1V, that means all connections are correct. Otherwise, please 

check if the wirings are connected correctly. 

b)

 

Turn on the output breaker of each UPS. 

c)

 

Turn on each UPS in turns. After a while, the UPSs will enter to AC mode synchronously and 

then, the parallel system is completed. 

6)   

Turn on the parallel system in Battery mode:

 

a)

 

Turn on the battery breaker (only available in long-run model) and output breaker of each UPS. 

NOTE: 

It’s not allowed to share one battery pack for long-run UPSs in parallel system. Each UPS 

should be connected to its battery pack. 

b)

 

Turn on any UPS. A few seconds later, the UPS will enter to battery mode. 

c)

 

Then, turn on another UPS. A few seconds later, the UPS will enter to battery mode and add to the         

parallel system.   

d)

 

If you have the third UPS, follow the same procedure of c). Then, the parallel system is complete.   

 

If more detailed information is needed, please contact supplier or service center for parallel 

operation instruction. 

2. Add one new unit into the parallel system 

1)    You can not add one new unit into the parallel system when whole system is running. You must cut 

off the load and shutdown the system.   

2)    Make sure all of the UPS are the parallel models, and follow the wiring refer to section 2-4. 
3)    Install the new parallel system refers to the previous section. 

3. Remove one unit from the parallel system 

There are two methods to remove one unit from the parallel system: 
First method: 

1)

 

Press the “OFF” key twice and each time should be lasted for more than 0.5s. Then, the UPS will 

enter into bypass mode or no output mode without output.   

2)

 

Turn off the output breaker of this unit, and then turn off the input breaker of this unit. 

3)

 

After  it  shuts  down,  you can  turn  off  the  battery breaker  (for  long-run model)  and remove  the 

parallel and share current cables. And then remove the unit from the parallel system. 

Summary of Contents for Centurion 10000 VA

Page 1: ...Centurion 10000 15000 20000 VA Tower Online UPS Users Manual www powershield com au...

Page 2: ...distortions The Centurions true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipme...

Page 3: ...and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through al...

Page 4: ...UPS INSTALLATION FOR PARALLEL SYSTEM 10 2 5 SOFTWARE INSTALLATION 12 3 OPERATIONS 13 3 1 BUTTON OPERATION 13 3 2 LED INDICATORS AND LCD PANEL 13 3 3 AUDIBLE ALARM 15 3 4 SINGLE UPS OPERATION 15 3 5 P...

Page 5: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over th...

Page 6: ...connect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040...

Page 7: ...Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only availab...

Page 8: ...ershield com au 7 Diagram 3 15K 20K Rear Panel Diagram 5 15KL 20KL Input Output Terminal Diagram 6 15K 20K Input Output Diagram 7 15K 20K Grounding Terminal Terminal Diagram 4 10K 10KL Input Output Te...

Page 9: ...execute the following instructions by professional personnel 1 Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or...

Page 10: ...s 5 Remove the terminal block cover on the rear panel of UPS Then connect the wires according to the following terminal block diagrams Connect the earth wire first when making wire connection Disconne...

Page 11: ...tall the battery pack Pay highly attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting simultane...

Page 12: ...rshield com au 11 NOTE The parallel system can not use one battery pack Otherwise it will cause system permanent failure 5 Refer to the following wiring diagram Wiring diagram of parallel system for 1...

Page 13: ...w powershield com au 12 Wiring diagram of parallel system for 15K L 20K L 2 5 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdo...

Page 14: ...utton to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key Press thi...

Page 15: ...ion Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates ove...

Page 16: ...seconds later UPS operates in Bypass mode and supplies power to the loads via the bypass NOTE When UPS is in Bypass mode the output voltage will directly power from utility after you switch on the in...

Page 17: ...buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery voltage drops to the alarm level the buzzer w...

Page 18: ...a fatal error in the UPS Users can get the fault code from display panel Please check the trouble shooting table in chapter 4 for details 2 Please check the loads wiring ventilation utility battery an...

Page 19: ...ctly b Turn on the output breaker of each UPS c Turn on each UPS in turns After a while the UPSs will enter to AC mode synchronously and then the parallel system is completed 6 Turn on the parallel sy...

Page 20: ...g UPS and the system will transfer to Bypass mode Set the maintenance switches from BPS to UPS and put the maintenance bypass covers back 5 Turn on the remaining UPS according to the previous section...

Page 21: ...utdown point for programmable output Y Y Y Y Y Y 12 Reserved Neutral loss detection Y Y Y Y Y Y 13 Battery voltage calibration Y Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y Y 15 Inverter voltage...

Page 22: ...UPS to CVCF mode If selected the output frequency will be fixed at 50Hz or 60Hz according to setting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not C...

Page 23: ...10 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low volt...

Page 24: ...setting point or shutdown time arrives the programmable output will be cut off automatically After the utility is recovering the output will turn on automatically If overload happens the programmable...

Page 25: ...nter key to make the CHE flash Secondly press the Enter key again to activate the neutral detection check If neutral is detected the alarm will be muted and the UPS will go back to normal mode If neut...

Page 26: ...hase difference between L2 and L1 with 120 L3 and L2 with 120 or phase difference between L2 and L1 240 and L3 and L2 with 240 3 8 Operating Mode Status Description Following table shows LCD display f...

Page 27: ...s the UPS has no output Alarm beeps every two minutes LCD display AC mode Description When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will...

Page 28: ...e UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode LCD display Battery mode Description When the input voltage is beyond the acceptable ra...

Page 29: ...the UPS will beep once and start Battery Test The line between I P and inverter icons will blink to remind users This operation is used to check the battery status LCD display Warning status Descript...

Page 30: ...over None 21 Battery SCR short circuited None 03 Bus under None 24 Inverter relay short circuited None 04 Bus unbalance None 29 Battery fuse broken in Battery mode None 06 Converter over current None...

Page 31: ...de Warning code Warning event Warning code Warning event 01 Battery unconnected 10 L1 IP fuse broken 02 IP Neutral loss or IP L2 L3 fuse broken 21 Line situations are different in parallel system 04 I...

Page 32: ...UPS output After repetitive overloads the UPS is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart...

Page 33: ...nnection If the connection is ok and the alarm is still displaying please refer to the LCD setting section to enter the neutral loss check menu to see if the parameter3 is CHE if it is please press th...

Page 34: ...nd with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery ter...

Page 35: ...Time 9 hours recover to 90 capacity Charging Current 1 0 A 10 max 2 0 A 10 max 2 0 A 10 max Charging Voltage 273 VDC 1 Long run Model Type Depending on applications Numbers 18 20 Charging Current 4 0...

Page 36: ......

Reviews: