background image

www.powershield.com.au 

 

12

 

3-4. UPS Operation 

1. Turn on the UPS with utility power supply (in AC mode)   

1)    After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the 

step only available for long-run model). Then set the input breaker at “ON” position. At this time 
the fan is running and the UPS supplies power to the loads via the bypass. The UPS is operating in 
Bypass mode.   

NOTE: 

When UPS is in Bypass mode, the output voltage will directly power from utility after you 

switch on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your 
precious devices, you should turn on the UPS. Refer to next step.   

2)    Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.     

3)  A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will 

operate in Battery mode without interruption. 

NOTE: 

When the UPS is running out battery, it will shut down automatically at Battery mode. When the 

utility power is restored, the UPS will auto restart in AC mode.   

2. Turn on the UPS without utility power supply (in Battery mode) 

1)    Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).   

2)    Press and hold the “ON” button for 0.5s to turn on the UPS, and the buzzer will beep once. 

3)    A few seconds later, the UPS will be turned on and enter to Battery mode. 

3. Connect devices to UPS 

After the UPS is turned on, you can connect devices to the UPS. 

1)    Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total 

load level.   

2)  If it is necessary to connect the inductive loads such as a printer, the in-rush current should be 

calculated carefully to see if it meets the capacity of the UPS, because the power consumption of 
this kind of loads is too big. 

3)    If the UPS is overload, the buzzer will beep twice every second. 

4)    When the UPS is overload, please remove some loads immediately. It is recommended to have the 

total loads connected to the UPS less than 80% of its nominal power capacity to prevent overload 
for system safety.   

5)    If the overload time is over acceptable time listed in spec at AC mode, the UPS will automatically 

transfer to Bypass mode.    After the overload is removed, it will return to AC mode. If the overload 
time is over acceptable time listed in spec at Battery mode, the UPS will become fault status. At this 
time, if bypass is enabled, the UPS will power to the load via bypass. If bypass function is disabled 
or the input power is not within bypass acceptable range, it will cut off output directly. 

4. Charge the batteries 

1)    After the UPS is connected to the utility power, the charger will charge the batteries automatically 

except in Battery mode or during battery self-test.   

2)  Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be 

shorter than expected time. 

3)    Make sure the battery numbers setting on the control board (Please refer to the section 3-4-12 for 

detailed setting) is consistent to real connection. 

Summary of Contents for Centurion PSCER10000

Page 1: ...Centurion 6000 10000 VA Rack Online UPS Users Manual www powershield com au...

Page 2: ...distortions The Centurions true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipme...

Page 3: ...ngs and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading throug...

Page 4: ...TION 7 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 UPS OPERATION 12 3 5 ABB...

Page 5: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over th...

Page 6: ...onnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1...

Page 7: ...One PowerShield NetGuard UPS monitoring software CD One RS 232 cable One USB cable One EPO plug Fitted on the rear panel NOTE Before installation please inspect the unit Be sure that nothing inside t...

Page 8: ...nput power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building befor...

Page 9: ...re installation NOTE Set the battery pack breaker in OFF position and then install the battery pack Pay attention to the rated battery voltage marked on the rear panel If you want to change the number...

Page 10: ...CVCF mode UP key Press this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9...

Page 11: ...cates that the UPS alarm is disabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information I...

Page 12: ...ce every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Yes Warning Overload Beeping twice every second Low battery Battery unconnected Over charge EPO enable Fan...

Page 13: ...e UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the...

Page 14: ...when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery self test 2 To keep the system reliable the UPS will perform the battery self test auto...

Page 15: ...battery and output immediately to avoid more risk or danger 12 Operation of changing battery numbers 1 This operation is only available for professional or qualified technicians 2 Turn off the UPS If...

Page 16: ...t 01 Output voltage Y 02 Output frequency Y 03 Voltage range for bypass Y 04 Frequency range for bypass Y 05 ECO mode enable disable Y 06 Voltage range for ECO mode Y 07 ECO mode frequency range setti...

Page 17: ...ting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not CVCF mode If selected the output frequency will synchronize with the input frequency within 46 54...

Page 18: ...Parameter 3 Set high voltage point for ECO mode 50 Hz Setting range is from 52 0Hz to 54 0 Hz 60 Hz Setting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz z 08 Bypass mode setting...

Page 19: ...programmable output Interface Setting These functions are not supported by the Rack model z 12 Reserved Interface Setting Reserve for future options z 13 Battery voltage adjustment Interface Setting...

Page 20: ...ttery specifications z 15 Output voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6 4V the default valu...

Page 21: ...de LCD display Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Bypass mode LCD display Desc...

Page 22: ...start failure 11 None Over temperature 41 None High Inverter voltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 Inverter output short circuited 14 3 9 Warning I...

Page 23: ...is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights o...

Page 24: ...most common problem 3 If the problem still persists please call 1300 305 393 for technical support or fill in the form in PowerShield web page for on line technical support Following details are need...

Page 25: ...nd with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery ter...

Page 26: ...recover to 90 capacity Charging Current 2 0 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 2 0 A 10 max Long run Model Charging Voltage...

Page 27: ...37 100350 00G...

Reviews: