3-8. Fault Code 

Fault event 

Fault code

Icon Fault event 

Fault code

Icon

Bus start failure 

01 

None Negative power fault 

1A 

None

Bus over 

02 

None Battery SCR short circuited 

21 

None

Bus under 

03 

None Inverter relay short circuited 

24 

None

Bus unbalance 

04 

None Battery voltage loss 

28 

Bus short circuited 

05 

None Output circuit circuited 

36 

None

Inverter soft start failure 

11 

None Over temperature 

41 

None

High Inverter voltage 

12 

None CPU communication failure 

42 

None

Low Inverter voltage   

13 

None Overload 

43 

Inverter output short circuited 

14 

 

 

 

3-9. Warning Indicator 

Warning Icon 

(flashing) 

Alarm 

Battery low 

 

 

Beeping every second 

Overload 

 

 

Beeping twice every second 

Battery unconnected 

 

 

Beeping every second 

Over charge 

 

 

Beeping every second 

EPO enable 

 

 

Beeping every second 

Fan failure/Over temperature 

 

 

Beeping every second 

Charger failure 

 

 

Beeping every second 

I/P fuse broken 

 

 

Beeping every second 

Overload 3 times in 30min 

 

Beeping every second 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Centurion PSCER10000

Page 1: ...Centurion 6000 10000 VA Rack Online UPS Users Manual www powershield com au...

Page 2: ...distortions The Centurions true online double conversion topology will continuously protect your equipment by internally isolating your equipment from the utility power ensuring that all your equipme...

Page 3: ...ngs and operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading throug...

Page 4: ...TION 7 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 LED INDICATORS AND LCD PANEL 9 3 3 AUDIBLE ALARM 11 3 4 UPS OPERATION 12 3 5 ABB...

Page 5: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over th...

Page 6: ...onnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1...

Page 7: ...One PowerShield NetGuard UPS monitoring software CD One RS 232 cable One USB cable One EPO plug Fitted on the rear panel NOTE Before installation please inspect the unit Be sure that nothing inside t...

Page 8: ...nput power source for the UPS as its rated current is less than the UPS s maximum input current Otherwise the receptacle may be burned and destroyed 2 Switch off the mains switch in the building befor...

Page 9: ...re installation NOTE Set the battery pack breaker in OFF position and then install the battery pack Pay attention to the rated battery voltage marked on the rear panel If you want to change the number...

Page 10: ...CVCF mode UP key Press this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9...

Page 11: ...cates that the UPS alarm is disabled Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information I...

Page 12: ...ce every 2 minutes Battery mode Beeping once every 4 seconds Fault mode Beeping continuously Yes Warning Overload Beeping twice every second Low battery Battery unconnected Over charge EPO enable Fan...

Page 13: ...e UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices one by one the LCD panel will display total load level 2 If it is necessary to connect the...

Page 14: ...when the UPS is running in AC mode CVCF mode ECO mode you could press the Test button to let the UPS do battery self test 2 To keep the system reliable the UPS will perform the battery self test auto...

Page 15: ...battery and output immediately to avoid more risk or danger 12 Operation of changing battery numbers 1 This operation is only available for professional or qualified technicians 2 Turn off the UPS If...

Page 16: ...t 01 Output voltage Y 02 Output frequency Y 03 Voltage range for bypass Y 04 Frequency range for bypass Y 05 ECO mode enable disable Y 06 Voltage range for ECO mode Y 07 ECO mode frequency range setti...

Page 17: ...ting in parameter 2 The input frequency could be from 46Hz to 64Hz NCF Setting UPS to normal mode not CVCF mode If selected the output frequency will synchronize with the input frequency within 46 54...

Page 18: ...Parameter 3 Set high voltage point for ECO mode 50 Hz Setting range is from 52 0Hz to 54 0 Hz 60 Hz Setting range is from 62 0Hz to 64 0Hz The default value is 52 0Hz 62 0Hz z 08 Bypass mode setting...

Page 19: ...programmable output Interface Setting These functions are not supported by the Rack model z 12 Reserved Interface Setting Reserve for future options z 13 Battery voltage adjustment Interface Setting...

Page 20: ...ttery specifications z 15 Output voltage adjustment Interface Setting Parameter 2 you may choose Add or Sub to adjust inverter voltage Parameter 3 the voltage range is from 0V to 6 4V the default valu...

Page 21: ...de LCD display Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Bypass mode LCD display Desc...

Page 22: ...start failure 11 None Over temperature 41 None High Inverter voltage 12 None CPU communication failure 42 None Low Inverter voltage 13 None Overload 43 Inverter output short circuited 14 3 9 Warning I...

Page 23: ...is locked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights o...

Page 24: ...most common problem 3 If the problem still persists please call 1300 305 393 for technical support or fill in the form in PowerShield web page for on line technical support Following details are need...

Page 25: ...nd with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery ter...

Page 26: ...recover to 90 capacity Charging Current 2 0 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 2 0 A 10 max Long run Model Charging Voltage...

Page 27: ...37 100350 00G...