Input Neutral
Input Line
B
Battery -
Output Neutral
Output Line
Terminal Block wiring diagram of 6KL/10KL
B
Battery -
Battery -
B
Terminal Block wiring diagram of Battery bank
NOTE 1:
Make sure that the wires are connected tightly with the terminals.
NOTE 2:
Please install the output breaker between the output terminal and the load, and the breaker
should be qualified with leakage current protective function if necessary.
6)
Insert the EPO plug into the EPO slot on the rear panel.
7)
Put the terminal block cover back to the rear panel of the UPS.
Warning:
(For connecting External battery bank )
●
For standard battery pack, there are one DC breaker to disconnect the battery pack and the UPS. But for
other external battery pack, make sure a DC breaker or other protection device between UPS and
external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before
installation.
NOTE:
Set the battery pack breaker in “OFF” position and then install the battery pack.
●
Pay attention to the
rated battery voltage
marked on the rear panel. If you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection
with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the
battery pack is correct.
●
Pay attention to the
polarity marking on external battery terminal block
, and make sure the
correct battery polarity is connected. Wrong connection may cause permanent damage of the UPS.
●
Make sure the
protective earth ground wiring is correct.
The wire current spec, color, position,
connection and conductance reliability should be checked carefully.
●
Make sure the
utility input & output wiring is correct
. The wire current spec, color, position,
connection and conductance reliability should be checked carefully. Make sure the L/N site is correct, not
reverse and short-circuited.
2-4. Software Installation
For optimal computer system protection, install PowerShield NetGuard UPS monitoring software to fully
configure UPS shutdown.