8. Battery replacement 

 

Defender  1200/1600  have  user  replaceable  battery  feature.  Please  read 

warning on the front page about battery safety and follow the steps carefully 

shown  below.  Please  use  only  PowerShield  approved  battery  pack  to 

maximize the performance of the unit. 

 

1. Shutdown    all connected equipment and turn the UPS off by pressing on / 

off button. 

2. Remove input cord from mains and remove all output cord from the UPS. 

3.  Flip  the  UPS  upside down.  There  is  a front  door  screw  found  on  the  front 

panel. Remove the screw using Philips screw driver. 

4.  Remove  the  front  panel  by  grabbing  the  bottom  edge  of  the  front  panel 

forward. Remove hooks from the enclosure. Please be careful not to apply 

excess  force  to  the  panel  as  it  may  cause  damage  to  the  LCD  cable 

attached to it. 

5. There is a metal plate holding the battery pack in the enclosure. Remove the 

metal plate from the unit. 

    6. Pull tag of the battery pack and remove the battery from the unit 

    7. Remove Red ( Positive )and Black ( Negative ) battery wires from the battery 

pack. 

    8.  Prepare  new  battery  pack.  Connect  Black  (  Negative  )  wire  to  the  new 

battery  black  terminal  and  connect  Red  (  Positive  )  battery  wire  to  the  red 

battery terminal. Note : You will see a small spark when you connect red wire 

to the battery. This is normal as the unit charges energy to some component. 

Please check polarity of battery terminals. 

9. Insert the battery back into the unit and put the metal plate back to the front 

of the enclosure. Place the front panel and screw the battery door screw.   

10. Please recharge the unit for 6 hours before you turn the unit on.   

9. Trouble Shooting 

 

Please  follow  the  trouble  shooting  section  below.  If  the  problem  cannot  be 

resolved, please check PowerShield FAQ web page or call our customer support 

for further assistance. 

Problem

Probable Causes

Solution

Low battery

Recharge the unit for at least 6 hours
and try to start it again.

Battery maybe faulty

Replace the battery with Powershield
battery kit.

Input circuit breaker tripped

Check circuit breaker at rear panel
and reset if it is tripped.

Continuous beeping
while unit utility is
normal

The unit maybe overloaded

Remove some equipment that is
connected to UPS outlets and check
load level indicator on LCD display.

Equipment maybe connected
to Surge protection outlets

The surge protection does not have
battery back up function. Connect
your equipment to UPS outlet if it is
required for battery back up.

The unit maybe overloaded

Remove some equipment that is
connected to UPS outlets and check
load level indicator on LCD display.

Low battery

Recharge the unit for at least 6 hours
and try to start it again.

Battery maybe fault

Replace the battery with PowerShield
battery kit.

Input circuit breaker tripped

Check circuit breaker at rear panel
and reset if it is tripped.

Input power cord maybe loose

Reconnect the power cord to wall
outlet properly.

LCD display not lit

Back up time is short /
none when power fails.

The unit stays on
battery when the utility
is normal

 

 
 
 
 
 
 

Summary of Contents for Defender 1200

Page 1: ...educe the risk of overheating of the product do not cover the cooling vent holes and avoid exposing the unit under direct sunlight or installing the unit near the heat emitting appliances such as heat...

Page 2: ...ings and other metal objects 2 Use proper tools with insulated handles 3 Do not lay tools or metal parts on the top of batteries 4 Disconnect charging source prior to connecting or disconnecting batte...

Page 3: ...onnect peripherals that do NOT need battery backup UPS and Surge Protection outlets These outlets provide battery backup power when main fails and unit is turned on Connect peripherals that need batte...

Page 4: ...unit will shut its output down On battery mode icon flashes Rapid beep one sec interval Overload status Total output power has exceeded the maximum power rating of the unit Load level indicator flash...

Page 5: ...he unit and put the metal plate back to the front of the enclosure Place the front panel and screw the battery door screw 10 Please recharge the unit for 6 hours before you turn the unit on 9 Trouble...

Page 6: ...er the phone with PowerShield technical support 5 If technical support found that the product is defective then the technical support will issue a Return Material Authorization Number RMA 6 If the uni...

Page 7: ...ime One PC load 120W Typical Recharge Time PROTECTION Full Protection Surge Protection Safety EMC OPERATING ENVIRONMENT Humidity Noise Level PHYSICAL Dimension D x W x H Net Weight 397 x 146 x 205 mm...