3.9 Battery connection

 

 

The UPS adopts positive and negative double battery framework, totally 16pcs(optional 18/20) in 

series.  A neutral  cable  is  retrieved  from  the  joint  between  the  cathode  of  the  8

th  

(9

th

/10 

th

)  and  the 

anode  of  the  9

th  

(10

th

/11 

th

)  of  the  batteries.  Then  the  neutral  cable,  the  battery  Positive  and  the 

battery  negative  are  connected  with  the  UPS  respectively.  The  battery  sets between  the  Battery 
anode and the neutral are called positive batteries and that between neutral and cathode are called 
negative ones. The user can choose the capacity and the numbers of the batteries according to their 
desire. 

 

External battery connections for long-run units. 

 

Note

 

 

 

 

The BAT+ of the UPS connect poles is connected to the anode of the positive 

battery, the BAT-N is connected to the cathode of the positive battery and the anode 

of the negative battery, the BAT- is connected to the cathode of the negative battery

 

Factory    setting    of    the    long-run    unit    is    battery    quantity---16pcs,    battery 
capacity---12V65AH(charger current 9.75A).  When connecting 18/20 batteries, please 
re-set  desired  battery  quantity  and  its  capacity  after  UPS  starts at  AC  mode.  Charger 
current  could  be  adjusted  automatically  according  to  battery  capacity  selected.  All 
related settings can be done through LCD panel or monitoring software 

 

 

CAUTION!

 

Ensure   correct   polarity   battery   string   series   connection.   i.e. 
inter-tier and inter block connections are from (+) to (-)terminals. 
Don’t mix batteries with different capacity or different brands, or 
even mix up new and old batteries, either.

 

 

 

WARNING!

 

Ensure  correct  polarity  of  string  end  connections  to  the  Battery 
Circuit  Breaker  and  from  the  Battery  Circuit  Breaker  to  the  UPS 
terminals  i.e.  (+)  to  (+)  /  (-)  to  (-)  but  disconnect  one  or  more 
battery cell links in each tier. Do not reconnect these links and do 
not  close  the  battery  circuit  breaker  unless  authorized  by  the 
commissioning engineer.

 

Summary of Contents for YDC3300

Page 1: ...ut high frequency online UPS designed by our R D team who is with years of designing experiences on UPS With excellent electrical performance perfect intelligent monitoring and network functions smart...

Page 2: ...onnection 9 3 10 UPS Multi Module Installation 10 3 11 Computer access 11 4 Operation 13 4 1 Operation Modes 13 4 2 Turn on off UPS 14 4 3 The LCD Display 19 4 4 Parameters setting 24 4 5 Display Mess...

Page 3: ...strongly poisonous and do harmful to body 4 Please avoid short circuit between anode and cathode of battery otherwise it will cause spark or fire 5 Don t disassemble the UPS cover or there may be an e...

Page 4: ...S system of which input current is kept in balance No unbalance problem might occur Digital Control This series UPS is controlled by Digital Signal Processor DSP ehance it increases reliability perfor...

Page 5: ...completely shut off when the EPO is pressed REPO function Remote EPO is also available in this series UPS 3 1 Unpack checking 3 Installation 1 Don t lean the UPS when moving it out from the packaging...

Page 6: ...d 8 Power Switch 9 REPO port 10 I P Switch 11 Terminal block for Input output battery 12 Intelligent Solt 1 SNMP card Relay card 13 Maintenance switch its cover 14 O P Switch 15 GND 3 4 LCD control pa...

Page 7: ...a normal installation the battery temperature is maintained between 15 C and 25 C Keep batteries away from heat sources or main air ventilation area etc WARNING Typical battery performance data are q...

Page 8: ...e current as listed below 3 7 Power Cables The cable design shall comply with the voltages and currents provided in this section Kindly follow local wiring practices and take into consideration the en...

Page 9: ...ine battery positive battery Neutral battery negative There are 3 connectors of GROUND under the terminal block Choose appropriate power cable Refer to the table above and pay attention to the diamete...

Page 10: ...gative battery the BAT is connected to the cathode of the negative battery Factory setting of the long run unit is battery quantity 16pcs battery capacity 12V65AH charger current 9 75A When connecting...

Page 11: ...reaker is in off position and there is no any output from each UPS connected Battery groups can be connected separately or in parallel which means the system itself provides both separate battery and...

Page 12: ...2 The outputs of all the UPS modules must be connected to a common output bus 3 The length and specification of power cables including the bypass input cables and the UPS output cables should be the s...

Page 13: ...nt Put the UPS name into Equipment Name and UPS ID address into Equipment address Click the button Append then the connection between UPS computer is accomplished CAUTION When the UPS worked on invert...

Page 14: ...the inverter to the bypass with power interruption to the critical AC load This is to avoid paralleling of unsynchronized AC sources This interruption is programmable but typically set to be less than...

Page 15: ...is safely isolated from the UPS output terminals Switch ON UPS input switch If the Rectifier input is within voltage range the rectifier will start up in 30 seconds then the inverter will start up aft...

Page 16: ...supply the load via Mains you may simply active the internal mechanical bypass switch CAUTION The load is not protected by the UPS when the internal mechanical bypass system is active and the power i...

Page 17: ...will be transferred from bypass mode to normal mode 4 2 4 Black Cold start procedure CAUTION Follow these procedures when the input AC Utility Failure but battery is normal Turn on the battery switch...

Page 18: ...ly isolate the UPS from AC Mains all input switches of Utility shall be completely off which includes the ones for rectifier and bypass The primary input distribution panel which is often located far...

Page 19: ...for the value then click Set as shown in below picture If the UPS sounds a beep that means the setting is correct At the window of Data Set click Ups ID write a value for the parallel UPS ID at the ri...

Page 20: ...described before CAUTION Parallel cable cannot be connected when setting the parallel parameters After setting the UPSes needed to be paralleled power off all the UPSes Connect all the UPSes according...

Page 21: ...ut B Output L2 Voltage Frequency 10 Output C Output L3 Voltage Frequency 11 Load A Load 12 Load B Load 13 Load C Load 14 Total Load Load 15 Temperature battery temperature need to connect batter senso...

Page 22: ...21 2 Phase A L1 Input Frequency 3 Phase B L2 Input Frequency 4 Phase C L3 Input Frequenc 5 Bat Positive 6 Bat Negative 7 Backup time...

Page 23: ...2 8 Phase A L1 Output Voltage Frequency 9 Phase B L2 Output Voltage Frequency 10 Phase C L3 Output Voltage Frequency 11 Phase A L1 Load Capacity 12 Phase B L2 Load Capacity 13 Phase C L3 Load Capacity...

Page 24: ...charging above 2 13 interface windows will also display the charging status at the same time as below Charging Status Boost Floating 3 Pressing scroll button you may circulate all messages from the fi...

Page 25: ...e 3 different modes for setting ECO PAL NOR press or to exit the mode setting save the mode setting and goes to output voltage setting or parallel redundancy quantity setting 4 4 2 Output voltage sett...

Page 26: ...UTION When powered by inverter it is necessary to turn off the inverter before setting voltage and frequency level 4 4 4 Battery capacity setting Battery capacity setting Note Inside the broken line i...

Page 27: ...attery capacity setting or bypass voltage upper limit setting 4 4 6 Bypass voltage upper limit setting Bypass voltage upper limit setting Note Inside the broken line is the flashing part When under th...

Page 28: ...e is 20 30 45 press or to exit the bypass voltage lower limit setting save the bypass voltage lower limit setting and goes to bypass upper limit setting or parallel ID setting 4 4 8 Buzzer Mute Settin...

Page 29: ...imit setting or parallel quantity setting CAUTION Parallel cable cannot be connected when setting the parallel parameters 4 4 10 Parallel quantity setting Parallel quantity setting Note Inside the bro...

Page 30: ...n alphabetical order This section is listed with each alarm message to help you troubleshoot problems Display messages Operational Status and Mode s Code ST Information stand for LED Fault Bypass Batt...

Page 31: ...Over temperature Twice per second Fault LED lit 21 Reserve Twice per second Fault LED lit 22 Battery reverse Twice per second Fault LED lit 23 Cable connection error Twice per second Fault LED lit 24...

Page 32: ...NetAgent II a versatile management tool NetAgent II also supports multiple languages and is setup for web based auto language detection Typical topology of the UPS Network Management Relay card The ca...

Page 33: ...32...

Page 34: ...rated frequency optional Battery Mode 50 60 0 2 Hz Crest Factor 3 1 THD 2 with linear load 5 with non linear load Efficiency 93 5 at normal mode 94 5 at normal mode Battery Voltage Standard unit 120Vd...

Page 35: ...N IEC 62040 2 EN IEC 62040 1 1 Appendix 2 Problems and Solution In case the UPS can not work normally it might be wrong in installation wiring or operation Please check these aspects first If all thes...

Page 36: ...d capacity set the correct data 6 Buzzer beeps every 0 5 seconds and LCD display output overload Overload remove some load 7 Buzzer long beeps LCD display 29 fault code The UPS output is in short circ...

Page 37: ...PC 5V Pin 2 Pin 2 PC DPLUS signal Pin 3 Pin 3 PC DMINUS signal Pin 4 Pin 4 Signal ground Available function of USB Monitor UPS power status Monitor UPS alarm info Monitor UPS running parameters Timin...

Page 38: ...ce s RS485 port and UPS RS485 port device RJ45 UPS RJ45 Description Pin 1 5 Pin 1 5 485 A Pin 2 4 Pin 2 4 485 B Available function of RS485 Monitor UPS power status Monitor UPS alarm info Monitor UPS...

Page 39: ...RS485 port and UPS s RS485 port Temperature sentor RJ45 UPS2 BAT_T RJ45 Description Pin 1 5 Pin 1 5 TX Pin 2 4 Pin 2 4 RX Pin 7 Pin 7 12V Pin 8 Pin 8 GND Available function of BAT_T Battery environme...

Page 40: ...ication port definition Definition of Male port Instruction UPS DB9 Instruction Pin1 UPS Battery Low Pin2 AC Power Failure Pin3 Turn off UPS Pin4 Common GND Function description Monitor UPS status Mon...

Page 41: ...ption Pin 1 Pin 1 EPO Pin 2 Pin 2 GND A remote emergency stop switch Dry contact signal and normally open not provided can be installed in a remote location and connection through simple wires to the...

Reviews: