4.4.7 Bypass voltage lower limit setting
Bypass voltage lower limit setting (Note: Inside the broken-line is the flashing part.)
When under the bypass voltage upper limit setting press On
▼
or when under parallel ID setting
press Off
▲
, it goes to the bypass lower limit setting. The bypass lower limit line flashes as in above
picture. (“-” for negative, positive does not have any symbol.)
①
use button Enter
to set the different
bypass voltage lower limit. The bypass voltage lower limit range is 20%,30%,45%.
②
press
▲
or
▼
to
exit the bypass voltage lower limit setting (save the bypass voltage lower limit setting) and goes to
bypass upper limit setting or parallel ID setting.
4.4.8 Buzzer Mute Setting
Buzzer Settings (note: red dashed box is the scintillation part
Press key ON under bypass volt-lo setting or press key OFF into buzzer setting under Parallel
operation ID setting. The scintillation of setting state shows as Figure 14 (Note: ON shows MUTE,
OFF shows NO MUTE).
①
press button Enter
for Mute Cycle Settings, mute choice has On and Off.
②
press button ON or OFF exits mute Setting (save mute setting state) and change to bypass volt-lo
setting or parallel operation ID Settings.