11
Load Break Switch Control
ERT-200S
2.3.
FRTU TECHNICAL SPECIFICATION
FRTU Technical Specification
Frequency
50 / 60 Hz System
Power Input
AC Voltage Power : 16Vac/32Vac
Power Output
Modem : DC 24V Max : 1A
Current Transformer Input
(CT: Current rate)
Current Input IA,IB,IC,IN,ZCT (Max : 13A)
Burden : Below than 0.5VA
Capacitor Voltage Divider
Inputs(CVD)
Input Rang : 2~6Vac
4Vrms at rated Phase Voltages
Burden : Below than 0.01VA
Output Contacts
Open/Close Operate Output : 240Vac 16A, 30Vdc 16A
Aux DO 1~4 : 250Vac3A, 30Vdc 3A
Input
Input 8 channel
Dry Contact Input Type
2.4.
Digital Process
2.4.1.
Digital Signal Controller(DSCs)
DSP Processor Feature
High-Performance 32-Bit CPU
•
TMS320F283X 32-Bit core
•
FPU : 150MHz
•
Six-Channel DMA Controller (for ADC, McBSP,
–
Up to 2 CAN Modules
•
ePWM, XINTF, and SARAM)
•
Harvard Bus Architecture
–
Up to 9 16-Bit
Timers
•
Fast Interrupt Response and Processing (6 for
ePWMs and 3 XINTCTRs)
•
Unified Memory Programming Model
•
DMA 6CH
•
On-Chip Memory : F28335, F28235:
–
One
Inter-Integrated-Circuit (I2C) Bus
•
256K x 16 Flash, 34K x 16 SARAM
•
Up to 6 Event Capture Inputs
•
Up to 2 Quadrature Encoder Interfaces