44
Load Break Switch Control
ERT-200S
Recloserlockout after a fault section, DAS indicates the fault section and isolates it by sending Open
command to the controllers of LBS L3, L4. Wherein L5 is to supply power from the back of a loop Tie
breaker.
i)
A fault detected between L3 and L4
ii)
Tripped Recloser(R1) in the line and L2,L3 indicate fault at the time
iii)
DAS decided the fault section and opened L3,L4, then closed R1, L5
L5 may be energized from the loop tie switch backward
[Fig. 6-1 ] Fault detection &restoration sequence
At the temporary fault,distribution lines are restored automatically by a reclosing. The fault indication
of FRTU can be reset by push button on the front panel or by remote reset command. Also, it can be
reset automatically when the line is energized.
[Fig. 6-2 ] Fault Indication