51
Load Break Switch Control
ERT-200S
Direction Detection
Off
On
On
On
Direction Voltage Pickup
5
85
10
1
%
Direction MTA
0
359
0
1
deg
Phase Fault / Function use
Range
Default
Step
1)
Set
[Use/No Use]
of direction Detection, when
occurs Phase fault.
2)
Display the “New Set”
3)
To save the changed “New Set”, selected
YES/NO
by using
[UP][DOWN]
and by pressing
[ENTER]
button, you can changed new setting value.
Phase Fault / Pick Up Current
Range
5 ~ 1300
Default
400A
Step
1A
Set Pick Up Current Setting.
# Fault current detection assurance range is 50A ~
13000A.
Phase Fault / Time
Range
0.05 ~ 10.00 sec
Default
0.05
Default
0.05
Set Detectiontime of Phase Fault element.
Phase Fault / Cold Load Pick UP
Range
100 ~ 500 %
Default
200%
Step
10%
Set Cold Load Pickup Multiplier.
Phase Fault / Cold Load Time