58
Load Break Switch Control
ERT-200S
Line Open / Function use
Range
Default
Step
Set
[Use / No Use]
of direction Detection, when occurs
Line Open detect.
7.1.6.
Sync. Check Setting
Sync. Check / Function use
Range
5 ~ 60 Deg
Default
30 Deg
Step
1 Deg
Set an alarm on the source side and load-side voltage
phase
Sync. Check / Function use
Range
0.1
~ 300.0 sec
Default
0.4
Default
0.1 sec
Set Delay time of Line Sync. detect element
Sync. Check / Function use
Range
Default
Step
Set
[Use / No Use]
of direction Detection, when occurs
Sync. Check.
Range
Step
Def.
Unit
Min
Max
Phase difference
5
60
1
30
Deg
Detection Time
0.1
300.0
0.1
0.4
sec
Function Use
No
Yes
No