63
Load Break Switch Control
ERT-200S
OFR / Pick-up Frequency Set
Range
50.00 ~ 70.00 Hz
Default
62.20Hz
Step
0.01Hz
Set Pickup Frequency.
OFR / Pick-up Voltage Set
Range
50 ~85 %
Default
80%
Step
1 %
Set pickup voltage.
OFR / Delay Time Set
Range
0.2
20.0 sec
Default
1.0 s
Step
0.1 s
Set Delay Time
OFR / Function use
Range
No Use / Use
Default
No Use
Step
Set
[Use / No Use]
of direction Detection, when occurs
Ground fault.
7.1.11.
Under Voltage Setting
Range
Step
Def.
Unit
Min
Max
V-PickUp
50
90
1
80
%
Delay Time
0.1
20.0
0.1
1.0
Sec
Function Use
No Use
Use
No Use