74
Load Break Switch Control
ERT-200S
Communication Config/ 3. TCP Control / 4. LAN Card Select
Range
1 ~ 2 Port
Default
1
Step
1
LAN Card Port Setting
(2 Port Option)
7.2.5.
DNP Parameter Setting
ERT-200Scan DNP3.0 communicate by using the communication port2. For more information refer the
“DNP3.0 Protocol Manual”
.
Item
Range
Default
Step
Unit
D/L Retries
0~2
0
1
D/L Timeout
0~255
0
1
sec
D/L Confirm
Yes/ No/Sometimes
No
A/L Retries
0~2
0
1
A/L Timeout
0~255
0
1
sec
Initial Unsolicited MSG
Yes/No
No
Unsolicited Class 1
Disable/Enable
Disable
Unsolicited Class 2
Disable/Enable
Disable
Unsolicited Class 3
Disable/Enable
Disable
Unsolicited Delay Time
0~60
0
1
sec
SBO Timeout
1~255
15
1
sec
Master Address set
0~65534
0
1
Slave Address Set
0~65534
4
1
Multi Frame Interval
10~500
100
1
ms
CommunicationConfig/ 4. DNP Parameter / 1. D/L Retry Set
Range
0 ~ 2
Default
0
Step
1
Set the retry number of Data Link.
CommunicationConfig/ 4. DNP Parameter / 2. D/L Timeout Set
Range
0~ 255 sec
Default
0
Step
1 sec
Summary of Contents for ERT-200S
Page 1: ...Feeder Remote terminal Unit ERT 200S Manual www powersys kr...
Page 13: ...13 Load Break Switch Control ERT 200S 2 5 Function BlockDiagram...
Page 38: ...38 Load Break Switch Control ERT 200S 5 3 3 Menu structure tree Figure Menu Tree Structure...
Page 42: ...42 Load Break Switch Control ERT 200S...
Page 96: ...Appendix 1 Drawings 1 Enclosure Control Cabinet...