75
Load Break Switch Control
ERT-200S
Set the waiting time of Data Link Frame transmission to
the Data Link Confirm (ACK) receiving of the master side.
ERT-200Sresends the Data Link Frame, when the Data Link
Confirm has not received during the setting time and it is
possible to retry the Data Link.
CommunicationConfig/ 4. DNP Parameter / 3. D/L Confirm Set
Range
Yes, No, Sometime
Default
No
Step
Choose whether Data Link Confirm is used or not.
NO :
Data Link Confirm is not used.
YES :
Data Link Confirm is used
Sometime :
When set the use of Data Link Confirm, check the setting
status of host and set same with the host. If the setting
status is different with the host can be occur an
communication error because of Data Link Reset.
CommunicationConfig/ 4. DNP Parameter / 4. A/L Retry Set
Range
0 ~ 2
Default
0
Step
1
set the Retry of A/L Confirm(ACK) receiving from Mast
Application to Slave Application.
CommunicationConfig/ 4. DNP Parameter / 5. A/L Timeout Set
Range
0 ~ 255 sec
Default
0
Step
1 sec
In case that request Confirm during the data transmission
from Slave Application to Master Application, set the
maximum time of A/L Confirm(ACK) receiving from Mast
Application to Slave Application.
CommunicationConfig/ 4. DNP Parameter / 6. Initial Unsol Set
Range
Yes, No
Default
No
Step
Summary of Contents for ERT-200S
Page 1: ...Feeder Remote terminal Unit ERT 200S Manual www powersys kr...
Page 13: ...13 Load Break Switch Control ERT 200S 2 5 Function BlockDiagram...
Page 38: ...38 Load Break Switch Control ERT 200S 5 3 3 Menu structure tree Figure Menu Tree Structure...
Page 42: ...42 Load Break Switch Control ERT 200S...
Page 96: ...Appendix 1 Drawings 1 Enclosure Control Cabinet...