76
Load Break Switch Control
ERT-200S
Select [YES/NO] of Initial Unsolicited Response Use when
Power Up.
YES : When Power Up, transmit the Initial Unsolicited
Response Message.
NO : When Power Up, do not transmit Initial Unsolicited
Response Message.
CommunicationConfig/ 4. DNP Parameter / 7. Unsol Delay Set
Range
0 ~ 60 sec
Default
0
Step
1 sec
Set the delay time of Unsolicited mode event
transmission to the master station. It is transmitted if
new event does not happen during this time.
CommunicationConfig/ 4. DNP Parameter / 8. SBO Timeout Set
Range
1 ~ 255 sec
Default
15
Step
1 sec
Set the time interval between Select Function and Operate
Function.
CommunicationConfig/ 4. DNP Parameter / 9. Master address Set
Range
0 ~ 65534
Default
0
Step
1