78
Load Break Switch Control
ERT-200S
Communication Config/ 4. IEC Parameter / 3. M_SP_Cyclic Setting
Range
Enable / Disable
Default
Disable
Step
When using IEC Protocol selection, Single Point Cyclic
data transmission setting.
Communication Config/ 4. IEC Parameter / 4. M_DP_Cyclic Setting
Range
Enable / Disable
Default
Disable
Step
When using IEC Protocol selection,
DoublePoint Cyclic data transmission setting.
Communication Config/ 4. IEC Parameter / 5. M_ME_Cyclic Setting
Range
Enable / Disable
Default
Disable
Step
When using IEC Protocol selection,
Measured value Cyclic data transmission setting.
Communication Config/ 4. IEC Parameter / 6. M_SP_Address Setting
Range
1-10000
Default
100
Step
Using IEC Protocol Single Point Base address setting.
Communication Config/ 4. IEC Parameter / 7. C_SC_Address Setting
Range
1-10000
Default
200
Step
Using IEC Protocol single command Base address setting.