81
Load Break Switch Control
ERT-200S
Communication Config/ 5. IEC 101 Parameter / 4. LINK Address Size
Range
1 ~ 2
Default
1
Step
Data Link Address Size.
Set the number of bytes for "Link address" field in an
IEC60870-5-101 Protocol.
Communication Config/ 5. IEC 101 Parameter / 5. ASDU Address Size
Range
1 ~ 2
Default
1
Step
ASDU Address Size
Set the number of bytes for the application layer
“
ASDU Address
”
field in an IEC 60870-5-101 message.
Communication Config/ 5. IEC 101 Parameter / 6. IOA Address Size
Range
1 ~ 3
Default
3
Step
Information Object Address Size
In IEC60870-5-104 IOA Address Size is Fixed 3.
Communication Config/ 5. IEC 101 Parameter / 7. COT Address Size
Range
1 ~ 2
Default
2
Step
COT Address Size
In IEC60870-5-104 COT Address Size is Fixed 2.
Communication Config/ 5. IEC 101 Parameter / 9. Link Mode Setting
Range
Unbalance / Balance
Default
Unbalance
Step
Set the Link mode in an IEC608705-101 Protocol.
ERT-200SControl only supports unbalanced mode.