72
Load Break Switch Control
ERT-200S
7.2.3.
Modem Control Setting
CommunicationConfig/ 2. Modem Control /1. Comm. Speed Set
Range
1200,2400,4800,9600, 19200bps
Default
9600 bps
Step
Select the Baud Rate of Port
CommunicationConfig / 2. Modem Control / 2. Comm. Line
Range
2Wire / 4Wire
Default
2 Wire
Step
Modem Communication line setting.
CommunicationConfig/ 2. Modem Control / 3. RTS Off Delay Set
Range
10 ~ 500 ms
Default
10 ms
Step
1 ms
RTS Off Delay Time set the delay time of RTS sign that
become Off after the data transmission.
It is time delay to prevent the liss if last data after sending
the data.
CommunicationConfig/ 2. Modem Control / 4. CTS Timeout Set
Range
1 ~ 255 sec
Default
1 sec
Step
1 sec
Set a Waiting time that waits Modems confirmation on
RTS signal which informs that ERT-200Sis ready to transfer
a data.
CommunicationConfig/ 2. Modem Control / 5. DCD Timeout Set
Range
100 ~ 30,000 ms
Default
100 ms
Step
100 ms