M520086-01
3-10
Individual current controls on both master and slave(s) remain active. See Figure 3-12 for
connection requirements.
3.1.9
Output overvoltage Protection
If the power supply is equipped with an overvoltage crowbar, the front panel will contain
overvoltage adjustment. The potentiometer controlling overvoltage may be adjusted
through an access hole in the front panel.
NOTE
All overvoltage circuitry has been properly adjusted
to their respective unit before leaving the factory.
For trip levels less than the maximum output voltage or to check the overvoltage circuitry,
perform the following procedure.
a.
Set the potentiometer fully clockwise.
b.
Adjust the power supply output voltage to the desired trip level.
c.
Slowly adjust the potentiometer counterclockwise until overvoltage is tripped.