Service Manual
Specification
Prelim Page ix
UPS Preliminary Pages
Issue 2 - November 2001
10kVA
15kVA
20kVA
30kVA
Bypass Data
Input Voltage Range For Bypass Switching
Nominal
±
10%
Overload Capability on Static Bypass
150% for 30 minutes, 1000% for 100 m seconds
Mechanical Data
Unit Dimensions (w x h x d)
530 x 1220 x 950 mm
Unit Weight Without Battery
185kg
Unit Weight With Standard Battery
275kg
365kg
365kg
455kg
Shipping Dimensions (w x h x d)
545 x 1260 x 965 mm
Unit Shipping Weight Without Battery
215kg
Unit Shipping Weight With Standard Battery
305kg
395Kg
395kg
485kg
Enclosure Rating
IP20
Colour
RAL 7035 Metal Covers
RAL 7042 Plastic Door
Design Standards
Safety
Radio Frequency Interference (RFI)
Electromagnetic Compatibility (EMC)
European Directive
Quality
EN50091Ć1Ć1
EN50091Ć2 Class A
CE marked compliance LVD / EMC
ISO9001