Issue 2 - November 2001
BATTERY AUTONOMY TIMES
Configuration
Part Nº
Approximate Autonomy Time in Minutes
at
Stated Load and 25
°
C
Configuration
Part N
100%
75%
50%
25%
10%
3 Phase 10kVA
UPS with 1 internal set of batteries
(Standard configuration)
6
9
17
35
115
UPS with 2 internal sets of batteries
+ 1 x BATT
17
24
40
82
282
UPS with 3 internal sets of batteries
+ 2 x BATT
28
41
66
133
486
UPS with 4 internal sets of batteries
+ 3 BATT
41
57
94
191
600
3 Phase 15kVA
UPS with 2 internal sets of batteries
(Standard configuration)
9
14
24
55
157
UPS with 3 internal sets of batteries
+ 1 x BATT
17
24
40
91
269
UPS with 4 internal sets of batteries
+ 2 x BATT
24
35
56
128
398
3 Phase 20kVA
UPS with 2 internal sets of batteries
(Standard configuration)
6
9
17
39
108
UPS with 3 internal sets of batteries
+ 1 x BATT
11
17
28
64
178
UPS with 4 internal sets of batteries
+ 2 xBATT
17
24
40
91
263
3 Phase 30kVA
UPS with 3 internal sets of batteries
(Standard configuration)
6
9
17
40
110
UPS with 4 internal sets of batteries
+ 1 x BATT
9
14
24
56
157