Service Manual
Chapter 2 - Installation
Battery Installation
2 - 7
3x3 UPS Installation
Issue 2 - November 2001
Figure 2-3
Battery Tray Installation for one battery string
Battery Fuses (shown removed)
Battery Earth Bar
Battery String Voltage Check
Note: Battery fuses are removed for transit and should only be fitted by the
commissioning engineer. The fuses can be found with the User manual, in
the document pocket on the battery safety cover.
Battery String Voltage check
1.
Ensure the battery fuses are removed from the switched fuse holders.
Warning
Do not fit the battery fuses into the fuse holders or close the fuse holders.
2.
With a DVM set to a DC range of above 450V, check for each individual battery string
voltage. This voltage for a serviceable battery should be b385V and +416V DC.
3.
Measure the battery string voltage from the lower connecting screw of the appropriate fuse
holder and the battery ćve connection bar. As shown in
Figure 2-3
4.
If a voltage of less than +385V is recorded reĆcheck the battery connections and reĆtest the
string voltage.
Note: A measured voltage substantially less then +385V DC may point to a
defective battery block this can be further isolated by disconnecting each
individual tray and carry out a further check of each tray voltage. This
should be grater than 132V for trays of 11 battery blocks and 120V for 10
blocks.