WARNING: 

 

In an emergency, main electric supply to the unit may cut off by unplugging the power 
cord A] Either from the wall outlet or from the appliance coupler of the units supplied 
with an appliance coupler and B] from the wall outlet only for the units supplied with a 
non-detachable power cord. Some models are offered with an on/off switch.  If you 
are using one of these unites, turn the power switch OFF. 

WARNING: 

 

Do not expose to temperatures below 0° Celsius (32°F) or above 65° Celsius (149°F). 
Do not expose this apparatus to relative humidity more than 95% RH (non-
condensing). 
Do not expose to pressure levels below 68.6 kPa or above 101.3 kPa.

 

WARNING: 

 

 
This apparatus is a Class 1 equipment. 

WARNING:   

 

 
Do not modify Isolation Station unit at any time during its entire service life. If the 
Isolation Station unit is modified by any manner for any purpose during its service life, 
user needs to carry out an evaluation to the requirements of the IEC 60601-1 
standard and relevant safety standards for the end application. 
 

WARNING:   

 

 
This unit is a multiple socket outlet [MSO] device. When user connects load 
equipment to Isolation Station (MSO) the total system becomes a new ME System 
and user needs to carry out an evaluation to the requirements of IEC 60601-1 
standard for the total system. 
 

 

POWER CORD REQUIREMENTS

        

  

 

Input

: All power cords must be appropriately approved by testing agencies in the country where the 

Isolation Station 

is Used, such as UL/CSA/VDE/SEMKO, etc. For the US and Canadian market, a 

HOSPITAL GRADE plug is required for medical applications. 
 
One end (plug) must be appropriate for the wall receptacle, while the other end is made to fit into the 
power inlet of the 

Isolation Station

, this end must be of appliance type, IEC-320 female plug. All power 

cords must have grounding. 
 
 

POWER

 

AWG (NOMINAL CROSS-

SECTIONAL AREA mm

2

Cu)

RECOMMENDED LENGTH

 

300VA

 

AWG 18 (0.75mm

2

Less Than 12 Feet

 

600VA

 

AWG 18 (0.75mm

2

Less Than 12 Feet

 

800VA

 

AWG 16 (1.25mm

2

Less Than 12 Feet

 

1000VA

 

AWG 16 (1.25mm

2

Less Than 12 Feet

 

1150VA

 

AWG 14 (2.0mm

2

Less Than 12 Feet

 

1500VA

 

AWG 14 (2.0mm

2

)

Less Than 12 Feet

 

1800VA

 

AWG 14 (2.0mm

2

)

Less Than 12 Feet

 

2400VA 

AWG 12 (3.0mm

2

)

Less Than 12 Feet 

3000VA 

AWG 10 (5.0mm

2

)

Less Than 12 Feet 

 

Summary of Contents for Isolation Station Series

Page 1: ...P2 POWERTRONIX Corporation Page 1 of 10 300VA 3000VA Instruction Manual ...

Page 2: ... shipping damage Do not install or operate the product if it appears to be damaged in any way If the unit is damaged notify the carrier and the company that sold you the unit IMMEDIATELY ENVIRONMENTAL ISSUES This power isolation unit has environmental requirements similar to other electronic equipment It has been designed for indoor use only in areas where it will not be exposed to excessive dust ...

Page 3: ...tics or other flammable gases or liquids WARNING Grounding continuity should be checked periodically NOTE USA and Canada grounding reliability can only be achieved when this equipment is connected to a matching receptacle marked Hospital Only or Hospital Grade WARNING The top and bottom surfaces of the power supply enclosure are not intended to be touched while the power supply is in use While the...

Page 4: ...y standards for the end application WARNING This unit is a multiple socket outlet MSO device When user connects load equipment to Isolation Station MSO the total system becomes a new ME System and user needs to carry out an evaluation to the requirements of IEC 60601 1 standard for the total system POWER CORD REQUIREMENTS Input All power cords must be appropriately approved by testing agencies in ...

Page 5: ...S WITH HIRE CURRENT RATINGS MOUNTING The Isolation Station may be placed horizontally on any flat and stable surface such as a floor or table top For high traffic areas carts and unstable surfaces use of the mounting brackets for all mounting locations is recommended to ensure the stability of the Isolation Station Some versions of the Isolation Station may also be vertically mounted to a wall For...

Page 6: ...s possible to the load equipment Do not use extension cords or surge or filtration devices with the power isolation unit Place all load equipment power switches in the OFF position Plug the power isolation unit into an appropriately sized AC power source Plug the load equipment into the power isolation unit receptacles The load equipment must be connected to the power isolation station unit with a...

Page 7: ...n a returned material authorization RMA number from customer support Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered as well as a purchase receipt or other proof of date and place of purchase Please keep your sales receipt or other document showing proof of purchase Attach it to this owner s manual and keep bot...

Page 8: ...ee cloth Do not use any cleaning agent as they may have a corrosive effect Use a soft lint free cloth or the dusting attachment or your vacuum cleaner to dust your power isolation unit Do not expose the power isolation unit to humidity rain sand or excessive heat caused by heating equipment or direct sunlight CONNECTION DIAGRAM ...

Page 9: ...CTION INFORMATION Date Purchased __________________________________________ Part Number __________________________________________ Serial Number __________________________________________ Where Purchased __________________________________________ ...

Page 10: ... its accompanying documentation without obligating POWERTRONIX to update information and or product that has been delivered earlier POWERTRONIX assumes no liability for typographical errors in this documentation POWERTRONIX shall not be liable for technical or editorial errors or omissions contained herein nor for incidental or consequential damages resulting from our furnishing of this material a...

Reviews: