INSTALLATION INSTRUCTIONS
2.1
GENERAL INFORMATIONS
This chapter describes the system installation procedures and lists the following subjects:
2.2 Reception and identification
2.3 Storage
2.4 UPS positioning
2.5 Room specifications
2.6 Arrangement and connection to mains
2.7 UPS Auxiliary connections
2.8 Earth connection
2.2
RECEPTION AND IDENTIFICATION
After removing the packing, visually inspect inside and outside the UPS and battery module (if included) to
check for any damage that could occur during shipping. If there is any damage, inform the shipper or
retailer immediately.
Check the supplied material against the packing slip.
The machine has an adhesive identification plate indicating the type, power and serial number; it is located
on the right door (fig.2.2).
2.3
STORAGE
If the system is not going to be installed immediately it must be stored in an environment with adequate
protection against excessive humidity and sources of extreme heat (from +5 to +40°C, humidity less than
95% without condensation).
If the battery module is supplied, also make sure that no more than 6 months pass between one
battery recharge and the next.
Once this period of time has elapsed, temporarily hook the UPS up to the
mains and run it for the time needed to recharge the batteries.
Fig. 2.2