R&D – PROCEDURA START-UP DT 0419 – E02
4.10
INSTRUCTIONS FOR RETURN FROM MANUAL BY-PASS MODE TO NORMAL OPERATION IN
POWER SAVE MODE
To return to normal operation from the manual bypass mode, proceed as follows:
1. Close the INPUT RESERVE (l2) switch
At this point, if the supply of the reserve line is present and within allowed range, the LCD display
will switch on and also all UPS circuits will init their operations.
2. Close UPS OUTPUT (l4) switch
3. Open MANUAL BY-PASS (l3) switch
At this point the load will be supplied from the reserve line.
Mount the padlock on the manual by-pass switch (l3)
4. Close the INPUT MAINS (l1) switch
Wait for about 10 seconds. In this time will be initiated progressive capacitors pre-charge process,
which protects the mains from overload.
The
INVERTER OFF
message will appear on the LCD.
5. Switch on the inverter
Using menu
1. CONTROL MODE
select
Inverter ON/OFF
and press ENTER
Check the correct operating status, indicated by the green LED on the control panel.
6. Battery connection
After checking the correct polarity of the batteries close the battery panel switch. It makes the
connection between the batteries and the UPS circuits.