Installation — International
Models:
No
Position
Function
1&2* OFF
230V
1
ON
2
OFF
240V
1
OFF
2
ON
220V
1&2
ON
230V w/ extended operating voltage range
3*
OFF
Enable site warning alarm
3
ON
Disable site warning alarm
4*
OFF
Approximately 2 minutes backup after low
battery alarm
4
ON
Approximately 5 minutes backup after low
battery alarm
5*
OFF
Enable <5% load auto shutdown
(after 5 mins on battery)
5
ON
Disable <5% load auto shutdown
6*
OFF
Conditional shutdown delay 5 sec.
6
ON
Conditional shutdown delay 180 sec.
7*
OFF
Not used
8*
OFF
Auto-frequency selection priority 50Hz
8
ON
Auto-frequency selection priority 60Hz
* These are the default values
International Dip Switch
Configurations
Set up the Dip Switches according to the
International Dip Switch Configurations table
below. If any switches are changed while the
unit is running, the changes will not take
effect until the unit is completely powered
down and then turned back on.
UPS Owner’s Manual
15
OFF
ON
1 2 3 4 5 6 7 8
☞
Dip Switches