42
SPECIFICATIONS CONT.
SINERGY III UPS (100 - 120 Volt UPS’s) specifications cont.
Sinergy III Series UPS
3000 VA Low Voltage
Model
Part Number
ACDEF3000-11
17301-01R / 17301-02R
Type
Sinergy III
Power Rating
3000 VA / 2700 W
Topology
On-Line Double Conversion
Input Voltage (Nominal)
Range
100-120 VAC
105-150 VAC
Input Frequency
50/60 Hz ±4
(Auto Sense on Start-Up)
Input Power Factor
>0.95
Input Current THD
<9.0%
Efficiency
>84.0%
Output Voltage
120 VAC (Default)
100/110/115 VAC (Selectable)
Output Current
25.0 A (Default)
30.0/27.3/26.1 A (Selectable)
Voltage Regulation
±1.0%
Overload
Online Mode
100-105%: Continuous; Warning Only
105-130%: 2 Minutes
130-200%: 10 Seconds
>200%: 250 Milliseconds
Overload
Battery Mode
100-105%: Continuous; Warning Only
105-130%: 10 Seconds
>130%: 250 Milliseconds
Overload
Bypass Mode
100-110%: Continuous; Warning Only
110-120%: 30 Minutes
120-130%: 10 Minutes
>130%: 1 Minute
Battery Voltage (Float / Nominal)
82.1/72.0 VDC
Charger Current
1.0 A
Backup Time (Full Load)
>3.6 Minutes
Shipping Weight
81.0 lbs. / 36.8 kg.
Communications Interface
USB / RS-232
Heat Dissipation (BTU/Hour)
1756 at 100% Load
11/2013 REV.
D
A03-00099
Summary of Contents for ACDEF1000-11