9
i
Ensure the Powervault G200 is completely isolated
from the mains supply and from the rotary isolator.
Follow local lock-out tag-out procedures
ii
If installation of emergency power socket (EPS) is
taking place after battery installation see Part 2 for
panel removal. Remove 3 screws on the right side
panel as shown in figure 6.
iii
Slide right side panel up and lift carefully (figure 7)
Caution: delicate wiring connected to the top
cover. Disconnect the earth connection and place
the panel in a safe place for the duration of the EPS
installation.
Powervault’s Emergency Power Socket (EPS) is not fitted as standard and Installers are therefore
occasionally required to fit this accessory to the Powervault if the customer has ordered it. The EPS gives
customers access to power available in the batteries during black outs; the EPS will be able to power basic
electrical appliances, provided the batteries have energy stored in them at the time, during emergencies and
when there is grid failure.
Part 3: Emergency Power Socket
(if purchased)
ELECTRICAL SAFETY
Ensure the Powervault G200 is completely
isolated from the mains supply.
FIGURE 6
FIGURE 7