Page 13
EN
8. Specifications
Model Name
DC UPS
INPUT
Nominal input voltage
230Vac
Acceptable Input Voltage Range
80~260Vac
Acceptable Input frequency Range
45Hz~65Hz
OUTPUT
Output power (max)
30W
Normal Voltage
12Vdc
Output Voltage Range
10.5V~13.8V
Line Mode Efficiency
> 80%
BATTERY
Type/Rating
12V/7Ah x 1pc
Discharge Prevention
10.5V ± 0.5V
Backup Time
(With 1A Discharging)
Typical 340mins
Rated Charging Voltage
13.7V ± 0.25V
Recharge Time (internal battery)
4 hours to 90% without load
after complete discharge
Charge Current
2.5A Maximum
Hot Swappable Battery
Yes
INDICATOR
AC mode
Green LED Lighting
Backup mode
Yellow LED Lighting
Battery low
Yellow LED Flashing
Battery replace
Red LED Flashing
Battery missing
Red LED Lighting
Fault
Red LED Lighting
Battery self-test
Green LED flashing
AUDIBLE ALARM
Backup mode
Sounding every 5 seconds
Battery low
Sounding every 1 second
Battery replace
Sounding every 2 seconds
Battery missing
Continuous sounding
Fault
Continuous sounding