24
Mo
de 1-1(single source)
Input: Connect ground cable (PE) to ground screw of chassis first;
Short terminal N/N with busbar #1, connect AC cable(N);
Short terminal mL1/bL1/mL2/bL2/mL3/bL3 with busbar #6, connect AC cable(L).
Output: Connect ground cable (PE) to ground screw of chassis first;
Short terminal N/N with busbar #1, connect AC cable(N);
Short terminal L1/L2/L3 with busbar #3, connect AC cable(L).
Mode 1-1(dual source)
Input: Connect ground cable (PE) to ground screw of chassis first;
Short terminal N/N with busbar #1, connect AC main source cable(N) and bypass
source cable(N);
Short input terminal mL1/mL2/mL3 with busbar #7, connect main source cable(L);
Short bypass terminal bL1/bL2/bL3 with busbar #5, connect bypass source cable(L).
Output: Connect ground cable (PE) to ground screw of chassis first;
Short terminal N/N with busbar #1, connect AC cable(N);
Short terminal L1/L2/L3 with busbar #3, connect AC cable(L).