PowerWalker VFI 1000-3000 AT 

Quick Guide 

LCD Panel 

The UPS has an LCD panel with 6 pages to scroll. 

 

Left side: Input Voltage 

[V] 

Right side: Output 

Voltage [V] 

 

Left side: Input frequency [Hz] 

Right side: Output frequency 

[Hz] 

 

Left side: Load level [%] 

Right side: Load in kW 

 

Left side: Load level [%] 

Right side: Load in kVA 

 

Left side: Battery capacity [%] 

Right  side: Battery voltage 

[VDC] 

 

Left side: Backup Time [min] 

Right side: Battery voltage 

[VDC] 

 

 

Modes and warnings 

Operation 

mode 

LCD display 

Description 

Line Mode 

 

Outlets supplied with power. Batteries are charged. 

Battery 

 

The unit provides output power from battery. 

ECO mode

[

1]

 

 

When the input voltage is within set range, UPS 

bypasses input to output for energy saving. 

[

1]

 

Bypass

[

2]

  

 

UPS bypasses voltage to output. 

Summary of Contents for VFI 1000 AT

Page 1: ...ft side Load level Right side Load in kVA Left side Battery capacity Right side Battery voltage VDC Left side Backup Time min Right side Battery voltage VDC Modes and warnings Operation mode LCD display Description Line Mode Outlets supplied with power Batteries are charged Battery The unit provides output power from battery ECO mode 1 When the input voltage is within set range UPS bypasses input ...

Page 2: ...thin range 3 Standby Output is switched off The batteries are charged EPO Emergency Power Off the UPS output is turned off Fault The UPS is in fault mode because of short circuit on the output Units defining the numeric value percentage kilowatt volt ampere minute hertz Fault Sound disabled Rear panel view ...

Page 3: ...PO Emergency Power Off Connector 7 USB port 8 Serial Port 9 Extension slot 10 Output sockets 11 Battery Pack connector 12 Output Terminal Block Battery Pack connection 1 Input connector 2 Fuse Board 3 Output connector Battery Packs are connected in parallel Grounding wire must be fixed to the housing ...

Page 4: ...g mode while in bypass mode or standby mode In setting mode click this button to confirm selection or press this button for 5 seconds to save the changes and exit the setting mode Press this button to scroll up in the LCD menu ESC button In setting mode click this button to display next selection or press this button for 5 seconds to exit setting mode without saving changes Press the button for 5 ...

Page 5: ...ption E11 E12 A62 Various issues related to batteries Please check if batteries are connected and they are in good condition E14 Issue related to the load Check if there is no short circuit or excessive load Test the UPS without the load E18 E19 A68 Issues related to overheating or fan failure Please check that the fan is rotating ventilation holes are not covered and the ambient temperature is wi...

Page 6: ...y Pack Battery Pack Connector available 5 PHYSICAL Dimension W x H x D mm 140 x 191 x 327 151 x 225 x 390 196 x 342 x 416 Net Weight kgs 14 5 17 14 21 3 Operation Humidity 20 90 RH 0 40 C non condensing MANAGEMENT Smart RS 232 or USB Supports Windows Linux Unix macOS and HID support for USB Software PowerMaster available at powermaster powerwalker com Optional SNMP Power management from SNMP manag...