Technical Specification 

MODEL 

VFI 1000 R1U 

POWER 

1000 VA / 800 W 

INPUT 

 
 

Voltage 
Range 

 

Low Line Transfer 

160VAC/140VAC/120VAC/110VAC ± 5% 

( based on load percentage) 

 

Low Line Comeback 

170VAC/150VAC/130VAC/120VAC ± 5% 

( based on load percentage) 

High Line Transfer 

300 VAC ± 5 % 

High Line Comeback 

290 VAC ± 5 % 

Frequency Range 

40Hz ~ 70 Hz 

Power Factor 

>

0.99 @ Nominal voltage (full load) 

OUTPUT 

Output voltage 

220/230/240 VAC ± 1% 

Frequency Range 

57 ~ 63 Hz (Synchronized Range) 

Frequency Range (Bat. Mode) 

60Hz ± 0.3 Hz 

Overload 

100%~105%: audible warning 

/105%-130%: 10s 

Current Crest Ratio 

3:1 

Harmonic Distortion 

<3 % (Linear Load) < 5 % (Non-linear Load) 

Transfer 
Time 

to Bat Mode 

Zero 

Inverter to Bypass 

4 ms (Typical) 

Waveform (Bat Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

~ 86% @ 100% load 

Battery Mode 

~ 83% @ 100% load 

BATTERY 

Battery  

4x 6V/7Ah 

Recharge Time 

4h to 90% 

PHYSICAL 

Dimension, D x W x H (mm) 

477 x 438 x 44 

Net Weight (kg) 

12.6 

Operation Humidity 

20-90 % RH @ 0-40°C (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

 

 

Summary of Contents for VFI 1000 R1U

Page 1: ... or transfer to bypass mode if bypass mode is enabled via software UPS Status LED Color Mode Line Mode LED1 Green Lighting LED4 to LED7 indicate load level during line mode LED4 75 load level LED5 50 75 load level LED6 25 50 load level LED7 0 25 load level Green Lighting Battery Mode LED2 Yellow Flashing LED4 to LED7 indicate battery Power during battery mode LED4 battery voltage 26V LED5 battery ...

Page 2: ...rnal battery connector III The pin assignment for dry contact Condition Pin status Yes No Low battery Pin 3 and Pin 9 are connected Pin 3 and Pin 1 are connected Output is abnormal Pin 7 and Pin 8 are connected Pin 7 and Pin 5 are connected Battery mode Pin 2 and Pin 6 are connected Pin 2 and Pin 4 are connected IV Disable Enable ROO RPO function Contact open UPS shuts down Contact closed UPS star...

Page 3: ...on de activate external remote contact Fault LED 3 will be OFF and restart the UPS by pressing button V Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously sounding Bypass Mode Sounding every 10 seconds ...

Page 4: ...ut voltage 220 230 240 VAC 1 Frequency Range 57 63 Hz Synchronized Range Frequency Range Bat Mode 60Hz 0 3 Hz Overload 100 105 audible warning 105 130 10s Current Crest Ratio 3 1 Harmonic Distortion 3 Linear Load 5 Non linear Load Transfer Time to Bat Mode Zero Inverter to Bypass 4 ms Typical Waveform Bat Mode Pure Sinewave EFFICIENCY AC Mode 86 100 load Battery Mode 83 100 load BATTERY Battery 4x...

Reviews: