21
13: Battery voltage calibration
Interface
Setting
Parameter 2: Select “Add” or “Sub” function to adjust battery
voltage to real figure.
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
14: Charger voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust charger
voltage
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
NOTE:
*Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
* Any modification should be suitable to battery specifications.
15: Inverter A voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter A
voltage.
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
* Add or Sub is according to the output voltage what you set.
16: Inverter B voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter B
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V and the
default value is 0V.
*It will display number 1 under
or
to represent
inverter B voltage.
17: Inverter C voltage adjustment
Interface
Setting
Parameter 2: you may choose Add or Sub to adjust inverter C
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default
value is 0V.
*It will display number 2 under
or
to represent
inverter C voltage.