background image

 

 

 

ENGLISH 

Setting correct EBM (External Battery Module) quantity is critical for reaching the desired 
backup time. Only if this value is set correctly, UPS will be able to maximize the battery 
usage. The value represents amount of original battery packs fitted with 2 strings of 9Ah 
batteries. 

XVII.

 

Configuring Load Segment 

Load  segments  are  groups  of  outlets  that  can  be  configured  through  the  display.  VFI  RT 
HID  models  have  two  configurable  load  segments.  When  UPS  is  turned  on  (it  has 
activated output), you can turn off a load segment. If the UPS is turned off (no output), 
then a load segment cannot be turned on. 

XVIII.

 

Bypass Mode 

If the bypass is set to enabled (value = 001), then the UPS would provide output to the 
load as long as there is input. Turning off the UPS would essentially switch off the inverter 
and supply unfiltered power to the load. 

XIX.

 

UPS Status Display String 

LCD Display String 

Description 

STbY 

UPS work at Standby mode (no output) 

LINE 

UPS work in Line mode 

bYPA 

UPS work in Bypass mode (no backup function!) 

bATT 

UPS work in Battery mode (no AC input) 

TEST 

UPS work in battery life/function test mode 

ECO 

UPS work in ECO mode 

CVCF 

UPS work in converter mode 

SITE 

Site fail, check input connection 

FANF 

Fan fail, check if fan is not blocked 

bLOW 

Battery low, recharge or replace batteries 

bOPN 

Battery open, check battery circuit connection 

bATF 

Battery fault, replace batteries 

EPO 

EPO, deactivate EPO 

OVLD 

Overload, disconnect load 

AMbH 

Ambient temperature too high 

For following errors contact our technical support: CHGF / TEPH / SHOR / ISFT / bSFT / OVTP / 
INVL / INVH / bUSH / bUSL / bUSE / bUSS / HIGH / NTCO 

XX.

 

Indicators and Audible alarm 

Audible alarm 

Backup Mode 

Sounding every 4seconds 

“bATT” on the screen 

Low Battery 

Sounding every second 

“bLOW” on the screen 

UPS Fault 

Continuously Sounding 

Red display 

Overload 

Sounding every second 

“OVLD” on the screen 

Battery Replacement 

Sounding every second 

Alarm  can  be  muted  when  it  is  activated,  but  it  will  sound  in  case  of  low  battery,  fan 
fault, overheat and other major fault. 

XXI.

 

Technical Specification 

Reviews: