FRANÇAIS
IX.
Spécifications Techniques.
MODÈLE
VI 1100 CW
VI 1500 CW
VI 2000 CW
VI 3000 CW
CAPACITÉ*
1100VA/770W
1500VA/1050W 2000VA/1400W
3000VA / 2100W
ENTRÉE
Plage de tension
d’entrée
162-290 VAC
Plage de fréquence
50/60 Hz ± 5 Hz (reglage automatique)
SORTIE
Tension de sortie
208*/220/230/240VAC
Regulation
de
tension AC
± 1.5% (Batt. Mode)
Plage de fréquence
synchronisation
47 ~ 53 Hz or 57 ~ 63 Hz
Plage Frequence
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
AVR boost/buck
-10%/+16% at 208V; -15%/+10% at 220V;
-15%/+10% at 230V; -15%/+10% at 240V
Current Crest Ratio
3:1
Harmonic
Distortion
≦
2 % THD (Linear Load) ; 5 % THD (Non-linear Load)
Temps de Transfert
Typical 2-6 ms, 10ms max.
Forme d’onde
Pure Sinewave
surcharge
LINE: 5min @ 103-120%; 10s @ 120-150%; 1s @ >150%
BAT: 1min @ 103-120%; 10s @ 120-150%; 0.5s @ >150%
rendement
Mode AC
>96% @ full charged battery
Mode ECO
>97% @ full charged battery
Mode Batterie
>88%
>90%
BATTERIE
Type de Batterie
12V/7AH
12V/9AH
12V/7AH
12V/9AH
Numbres
2
4
Temps de Recharge
4 Heures pour atteindre 95 % de capacité de battérie interne
Courant de charge
1.4 A
CARRACTÉRISTIQUES PHYSIQUES
Dimensions DxWxH
397 X 145 X 220
455 X 145 X 220
Poids net (kgs)
11.65
12.35
18.1
20.3
ENVIRONMENT
Humidité de
fonctionnement
20-95 % RH @ 0- 40°C (sans-condensation)
Niveau sonore
Moins de 45dBA @ á 1m (avec contrôle automatique de la vitesse
du ventilateur)
Gestion
USB avec HID
Supporte Windows, Linux, Unix etMAC
* Régler la capacité à 80% lorsque la tension de sortie est réglée à 208VAC.
Summary of Contents for VI 1100 CW
Page 1: ...Quick Guide PowerWalker VI CW Series EN DE FR IT PL RU...
Page 45: ...0 24 25 49 50 74 75 100 III 1100 1500 BA 2000 3000 BA 1 2 3 4 EPO 5 USB 6 RS 232 7 SNMP 8...
Page 46: ...IV USB RS 232 USB RS 232 V AVR AVR 10 2 43 2 10 2...
Page 47: ...27 2 2 EPO 2 41 2 45 2 2 2 EEPROM 2 VI ON Mute 2 3 ON Mute 3 ECO OFF Enter 2...