ENGLISH
Quick Guide
PowerWalker VI CW Series
I.
Setup Requirements
1. Leave sufficient space around for air circulation (recommended 10cm in front, 30cm
in the back and 30cm on sides)
2. Keep ambient temperature below 40ºC. Between 40-50ºC the UPS will gradually
derate the maximal Power reaching 70% at maximal 50ºC.
3. Install the UPS at maximum altitude of 1000m. Between 1000-5000m the UPS will
gradually derate the maximal Power reaching 65% at 5000m.
II.
LCD Panel
Display
Function
Indicates the estimated backup time. H: hours, M: minute, S: second.
Indicates the configuration items
Indicates the warning and fault codes
Indicates that the UPS alarm is disabled.
Indicates the input voltage, input frequency, input current, battery voltage,
battery current, battery Power, ambient temperature, output voltage,
output frequency, load current and load percent.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
Indicates overload.
Indicates that programmable management outlets are working.
Indicates the UPS connects to the mains.
Parameter 1
Parameter 2