ENGLISH
VII.
UPS Settings
Parameter 1
Parameter 2
01
Output voltage setting
208/220
/230/240
Value in V AC
02
Programmable outlets
ENA/dIS
Enable or Disable (default).
03
Settings of programmable outlets
0-999
Backup time limit for programmable outlets
(default 999)
04
This is reserved position, changing the value will not have any effect
06
Limitation setting for autonomy time
0-999/dIS
Limit in minutes; 0 actually means 10s
07
This is reserved position, changing the value will not have any effect
08
EPO logic setting
AO
Normally Open (default). EPO will be activated
if pins 1 and 2 are not shorted
AC
Normally Closed. EPO will be activated if pins 1
and 2 are shorted
00
Exit Settings
VIII.
Programmable Outlets
The settings can be only changed in Standby Mode. After you setting the time limit, Exit the
Settings (Menu 00) and disconnect input, wait until it shuts off completely. Settings will be
saved after the UPS is turned on again.
IX.
Site Wiring Fault
“Site Wiring Fault” can be disabled via software. Please check software manual for details.
X.
Technical Specification
MODEL
VI 1100 CW
VI 1500 CW
VI 2000 CW
VI 3000 CW
POWER*
1100VA/770W
1500VA/1050W 2000VA/1400W
3000VA / 2100W
INPUT
Acceptable Voltage
162-290 VAC
Frequency Range
50/60 Hz ± 5 Hz (auto sensing)
OUTPUT
Output voltage
208*/220/230/240VAC
AC
Voltage
Regulation
± 1.5% (Batt. Mode)
Frequency
Synchronized
Range
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
AVR boost/buck
-10%/+16% at 208V; -15%/+10% at 220V;
-15%/+10% at 230V; -15%/+10% at 240V
Current Crest Ratio
3:1
Summary of Contents for VI 1100 CW
Page 1: ...Quick Guide PowerWalker VI CW Series EN DE FR IT PL RU...
Page 45: ...0 24 25 49 50 74 75 100 III 1100 1500 BA 2000 3000 BA 1 2 3 4 EPO 5 USB 6 RS 232 7 SNMP 8...
Page 46: ...IV USB RS 232 USB RS 232 V AVR AVR 10 2 43 2 10 2...
Page 47: ...27 2 2 EPO 2 41 2 45 2 2 2 EEPROM 2 VI ON Mute 2 3 ON Mute 3 ECO OFF Enter 2...