External battery cabinet option
It’s recommended to install external battery cabinets next to the UPS unit. The external battery
can be placed on either side of the UPS unit. Check before the installation that the battery
voltage values in the type plate of the UPS and external battery cabinets are the same. The
cables are delivered with the external battery cabinet. See External Battery Cabinet (EBC)
installation procedure.
Warning!
The UPS contains high DC voltages. A qualified person must do the connections between
the UPS and the external battery cabinet(s). The battery cabinet is connected electrically
in parallel with the internal batteries of the UPS.
Figure11.
UPS and external battery cabinets.
Battery racks
External battery racks shall be sized to take the voltage drop in the cable into account. To
obtain support and help contact the local office or agent authorised by the manufacturer.