DESCRIPTION:
DRAWING NO:
SHEET:
SSBM CUSTOMER INTERFACE PANEL
5 of 6
164201373---4
A---17
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
Table J. Customer Interface Panel Inputs and Outputs
Terminal
Block
TB Pin #
Name
Description
1
CHANNEL A POWERNET --- HIGH
Channel A connection of PowerNet from UPS
2
CHANNEL A POWERNET --- LOW
Channel A connection of PowerNet from UPS
Modules. Used to control and monitor UPS
3
CHANNEL A POWERNET --- GND
Modules. Used to control and monitor UPS
modules.
4
NOT USED
TB1
5
NOT USED
TB1
6
CHANNEL B POWERNET --- HIGH
Channel B connection of PowerNet from UPS
7
CHANNEL B POWERNET --- LOW
Channel B connection of PowerNet from UPS
Modules. Used to control and monitor UPS
8
CHANNEL B POWERNET --- GND
Modules. Used to control and monitor UPS
modules.
9
EPO TO UPS MODULE --- RTN
Emergency Power Off control connections for
10
EPO TO UPS MODULE
Emergency Power Off control connections for
UPS modules
1
REMOTE EPO
Contacts used to activate remote EPO of SSBM
2
REMOTE EPO RTN
Contacts used to activate remote EPO of SSBM
and UPS.
3
NOT USED
4
NOT USED
TB2
5
BLDG ALARM 1
Programmable UPS alarm. Activated by a remote
TB2
6
BLDG ALARM 1 RTN
Programmable UPS alarm. Activated by a remote
contact closure. (See Note 1)
7
BLDG ALARM 2
Programmable UPS alarm. Activated by a remote
8
BLDG ALARM 2 RTN
Programmable UPS alarm. Activated by a remote
contact closure. (See Note 1).
9
BLDG ALARM 3
Programmable UPS alarm. Activated by a remote
10
BLDG ALARM 3 RTN
Programmable UPS alarm. Activated by a remote
contact closure.
1
BLDG ALARM 4
Programmable UPS alarm. Activated by a remote
contact closure Default is Go to Bypass
2
BLDG ALARM 4 RTN
contact closure. Default is Go to Bypass.
(See Note 2 and 3)
3
BLDG ALARM 5
Programmable UPS alarm. Activated by a remote
contact closure Default is Go to UPS
4
BLDG ALARM 5 RTN
contact closure. Default is Go to UPS.
(See Note 4)
TB3
5
BLDG ALARM 6
Programmable UPS alarm. Activated by a remote
TB3
6
BLDG ALARM 6 RTN
Programmable UPS alarm. Activated by a remote
contact closure. Default is on Generator.
7
NOT USED
8
NOT USED
9
NOT USED
10
NOT USED
NOTES:
1.
If the SSBM is equipped with an optional System Maintenance Bypass (SMB), Building Alarms #1
and #2 are used for the MIS and MBP breakers shown on the Monitor Panel Mimic and are
unavailable for customer use.
2.
If the SSBM is setup for Powerware Sync Control, Building Alarm #4 is used for the “Sync Control
Trouble” alarm and is unavailable for customer use.
3.
If the SSBM is setup for Powerware Hot-Tie Control, Building Alarm #4 is used for the programmed
control function “Hot-Tie Trouble” and is unavailable for customer use.
4.
If the SSBM is setup for Powerware Sync Control or Hot-Tie Control, Building Alarm #5 is used for
the programmed control function “Transfer to Bypass Disabled” and is unavailable for customer
use.