2 of 2
PHYSICAL FEATURES AND REQUIREMENTS
062504
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
A
164201535---2
Installation Information
A-4
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual
S
164201535 Rev A
6.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
0---40
˚
C (32---104
˚
F)
Recommended Operating Range:
20---25
˚
C (68---77
˚
F)
Maximum Relative Humidity:
95%, noncondensing
The UPS ventilation requirements are shown in Table C.
Table C. Air Conditioning or Ventilation Requirements During Full Load Operation
Ratings
Input/Output Voltage
Heat Rejection
BTU/hr
¢
1000/hr (Kg---cal/hr)
40 kVA
208/208
11.8 (2.98)
40 kVA
480/480
10.9 (2.76)
80 kVA
208/208
27.2 (6.86)
80 kVA
480/480
22.4 (5.64)
Ventilation required for cooling air exhaust: approximately 4.72 liter/sec (1000 cfm).