POWER WIRING INSTALLATION NOTES
062504
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
A
164201535---5
NOTE
: Customer ground, size 2/0, can be
run in any conduit listed in Table I.
Installation Information
A-9
Powerware
®
9390 UPS (40–80 kVA) Installation and Operation Manual
S
164201535 Rev A
8.
Terminals are UL and CSA rated at 90
˚
C. Refer to Table G and Table H for power cable
terminations, and Table I for conduit requirements. Drawing 164201535---7 shows the
location of the power cable terminals inside the UPS cabinet.
Table G. UPS Cabinet Power Cable Terminations 9390--80/40 and 9390--80/80 208V/208V
Terminal Function
Terminal
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input to UPS Rectifier
S
E6
Phase A 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
p
and Bypass (Single Input)
E7
Phase B 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
E8
Phase C 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
AC Input to UPS Rectifier
C
E1
Phase A 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
p
(CB1)
(Dual Input)
E2
Phase B 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
(Dual Input)
E3
Phase C 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
AC Input To Bypass (Dual
E6
Phase A 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
p
yp
(
Input)
E7
Phase B 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
E8
Phase C 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
Single Feed Jumper from
—
Phase A
N/A
22.6 (200)
M10 Hex Bolt
g
p
Rectifier Input Terminals to
Bypass Input Terminals
—
Phase B
N/A
22.6 (200)
M10 Hex Bolt
Bypass Input Terminals
—
Phase C
N/A
22.6 (200)
M10 Hex Bolt
AC Output to
C
E9
Phase A 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
p
Critical Load
E10
Phase B 1 ---#6---350 kcmil
42.4 (375)
3/8 in. Hex
E11
Phase C 1 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
DC Input from
S
E4
Positive
1 --- #6---350 kcmil
31.1 (275)
5/16 in. Hex
p
Battery to UPS
E5
Negative 1 --- #6---350 kcmil
31.1(275)
5/16 in. Hex
Input and Output Neutral
E12
Neutral
8 --- #6---350 kcmil
42.4 (375)
3/8 in. Hex
Customer Ground
Ground
Ground
8 --- #14---1/0
5.6 (50)
Slotted