POWER WIRING INSTALLATION NOTES
A
B
C
D
A---5
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
Table F. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware BPIV---30/20
(Without Options Cabinet)
Ratings
Units
Rating 50/60 Hz
Basic unit ratings at
0.9 lagging PF load
KVA
KW
20
18
gg g
INPUT/OUTPUT
VOLTAGE
208
AC Input to UPS Rectifier
(0.95min.PF)
Amps*
70
AC
AC Input to UPS Rectifier
(0.95min.PF)
3
, 1 gnd
Amps*
70
AC
INPUT
3
, 1 gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
3 (1)
*(Maximum amps includes full load current plus
battery recharge current)
AC
AC Input to Module Bypass (UPS Bypass)
Full Load Current
3
, (1) Neutral, (1) gnd
Amps
55.5
AC
INPUT
Full Load Current
3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
4 (1)
DC
INPUT
DC Input from External Battery Source to UPS
(1) positive, (1) negative, (1) gnd
VDC (Nominal)
Amps
288
68
INPUT
( ) p
, ( )
g
, ( ) g
Minimum conductor size (number per pole
)
(See note 8)
AWG or kcmil(ea)
3 (1)
AC
AC Output to Critical Load
Full Load Current 3
(1) Neutral (1) gnd
Amps
55.5
AC
OUTPUT
Full Load Current 3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
4 (1)
Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware BPIV---30/25
(Without Options Cabinet)
Ratings
Units
Rating 50/60 Hz
Basic unit ratings at
0.9 lagging PF load
KVA
KW
20
22.5
gg g
INPUT/OUTPUT
VOLTAGE
208
AC Input to UPS Rectifier
(0.95min.PF)
Amps*
90
AC
AC Input to UPS Rectifier
(0.95min.PF)
3
, 1 gnd
Amps*
90
AC
INPUT
3
, 1 gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
2 (1)
*(Maximum amps includes full load current plus
battery recharge current)
AC
AC Input to Module Bypass (UPS Bypass)
Full Load Current
3
, (1) Neutral, (1) gnd
Amps
69.4
AC
INPUT
Full Load Current
3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
4 (1)
DC
INPUT
DC Input from External Battery Source to UPS
(1) positive, (1) negative, (1) gnd
VDC (Nominal)
Amps
288
85
INPUT
( ) p
, ( )
g
, ( ) g
Minimum conductor size (number per pole
)
(See note 8)
AWG or kcmil(ea)
2 (1)
AC
AC Output to Critical Load
Full Load Current 3
(1) Neutral (1) gnd
Amps
69.4
AC
OUTPUT
Full Load Current 3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
4 (1)