DESCRIPTION:
DATE:
DRAWING NO:
1 of 2
SHEET:
REVISION:
C
013004
PHYSICAL FEATURES AND REQUIREMENTS
164201406---3
A---21
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
1.
The UPS equipment operating environment must meet the size and weight requirements
shown in Table X, according to your UPS system configuration.
2.
In the UPS system, the UPS, Options, and Battery cabinets are palleted separately for
shipping.
3.
Do not tilt cabinets more than
10
˚
during handling.
4.
Dimensions are in millimeters (inches).
Table X Equipment Weight
Table X. Equipment Weight
Component
Weight
Kg (lb)
Component
Shipping
Installed
Point Loading
UPS Cabinet with Filter and Batteries
Powerware BPIV (10 kVA---15 kVA)
461 (1017) 435 (958)
6 at 73 (160)
UPS Cabinet with Filter and Batteries
Powerware BPIV (20 kVA---30 kVA)
873 (1925) 838 (1847)
9 at 93 (205)
Options Cabinet with PDM and no transformer
Powerware BPIV (10 kVA---15 kVA)
118 (260)
90 (200)
4 at 23 (50)
Options Cabinet with PDM and 1 transformer
Powerware BPIV (10 kVA---15 kVA)
240 (530)
213 (470)
4 at 53 (118)
Options Cabinet with PDM and 2 transformers
Powerware BPIV (10 kVA---15 kVA)
358 (790)
331 (730)
4 at 83 (183)
Options Cabinet with PDM and no transformer
Powerware BPIV (20 kVA---30 kVA)
154 (340)
120 (265)
6 at 20 (44)
Options Cabinet with PDM and 1 transformer
Powerware BPIV (20 kVA---30 kVA)
471 (1040) 437 (965)
6 at 73 (161)
Options Cabinet with PDM and 2 transformers
Powerware BPIV (20 kVA---30 kVA)
782 (1725) 748 (1650)
6 at 125 (275)
Battery Cabinet
361 (795)
333 (735)
6 at 56 (123)
NOTES:
Powerware BPIV (10 kVA---15 kVA)
1. For UPS Cabinet without Filter, subtract 25 Kg (55 lb).
2. For UPS Cabinet without Batteries, subtract 227 Kg (499 lb)
3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)
4. For Options Cabinet with Distribution Housing, add 11 Kg (25 lb)
Powerware BPIV (20 kVA---30 kVA)
1. For UPS Cabinet without Filter, subtract 41 Kg (90 lb).
2. For UPS Cabinet without Batteries, subtract 453 Kg (998 lb)
3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)
5.
The clearances required around the UPS System are shown in Table Y.
Table Y. System Clearances
From Front of Cabinet
36 inches working space
From Back of Cabinet
12 inches air circulation clearance
From Sides of Cabinet
Allow space for Options and Battery Cabinets