PHYSICAL FEATURES AND REQUIREMENTS
164201406---3
A---22
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
6.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
0---40
˚
C (32---104
˚
F)
Recommended Operating Range:
20---25
˚
C (68---77
˚
F)
Maximum Relative Humidity:
95%, noncondensing
The UPS ventilation requirements are shown in Table Z.
Table Z. Air Conditioning or Ventilation Requirements
During Full Load Operation
Powerware BPIV (10 kVA--30 kVA)
Ratings
Input/Output Voltage
Heat Rejection
BTU/hr
¢
1000/hr (Kg---cal/hr)
208/208
2.7 (0.7)
10 KVA
480/208
3.4 (0.9)
480/480, 600/208
3.9 (1.0)
208/208
4.0 (1.0)
15 KVA
480/208
5.1 (1.2)
480/480, 600/208
5.8 (1.4)
208/208
5.3 (1.3)
20 KVA
480/208, 600/208
6.7 (1.6)
480/480
7.7 (1.9)
208/208
6.7 (1.7)
25 KVA
480/208, 600/208
8.5 (2.1)
480/480
9.7 (2.4)
208/208
8.1 (2.1)
30 KVA
480/208, 600/208
10.2 (2.6)
480/480
11.7 (3.0)