A---28
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
C
ONELINE DRAWINGS OF UPS SYSTEM
1 of 1
093003
UPS CABINET
INVERTER
RECTIFIER
CB1
STATIC
SWITCH
BACKFEED
CONTACTOR
(K5)
RS--- 232
REMOTE EPO
BUILDING ALARMS
COMMUNICATIONS
SERVER
AC OUTPUT
TO
CRITICAL LOAD
OUTPUT
CONTACTOR
OUTPUT FILTER
(K3)
D
C
AC INPUT TO
UPS RECTIFIER
3 WIRE A---B---C
AC INPUT
TO BYPASS
4 WIRE A---B---C
ROTATION
ROTATION
SEE NOTE 1
B
A
NOTE 1: Remove jumper for dual feed.
(See Tables U, V, and W)
INPUT FILTER
OPTIONAL
UPS SYSTEM WITH 208V INPUT AND 208V OUTPUT,
SINGLE OR DUAL FEED
POWERWARE BPIV (10 kVA---15 kVA)
POWERWARE BPIV (20 kVA---30 kVA)
INPUT
CONTACTOR
(K1)
BATTERY
SWITCHES
INTERNAL
BATTERY
DC---DC
CONVERTER
(K2)
BATTERY
CABINET
EXTERNAL
BATTERY
BATTERY
BREAKER
BATTERY
BREAKER
GENERAL
PURPOSE RELAYS
CAN INTERFACE
X-SLOT
INTERFACE
(Optional)
164201406---6
MAINTENANCE
BYPASS
SWITCH
(DUAL FEED)
AC INPUT TO
UPS RECTIFIER
(SINGLE OR DUAL FEED)
(SINGLE FEED)
CB2
FUSE
FUSE
REMOTE
BATTERY
INPUT
E1, E2, E3
E6, E7, E8, E12
E9, E10,
E11, E12
E4. E5