Communication
63
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA)
Uncontrolled Copy
Communications Mode Reference Chart
The following chart defines the UPS serial port contacts. Serial
communication is not available with 3Com and AS/400 network
configurations. Use only the applicable pins for the selected
communication mode; otherwise, interference problems may occur.
Communication Mode Function
Signal Name Pin No.
True Condition
Serial
Data to UPS
RS232 TxD
2
N/A
Data from UPS
RS232 RxD
3
N/A
Signal Ground
7
Novell
(D f l )
Battery On
ON.AC
14/16
Open
(Default)
Low Battery
TWO.MIN
23/24
Closed
Signal Ground
7/15/25
Novell
(C
)
Battery On
ON.AC
14/16
Closed
(Custom)
Low Battery
TWO.MIN
23/24
Closed
Signal Ground
7/15/25
3Com
(D f l )
Shutdown (Remote)
SHUT.DOWN
2
Positive Voltage
(Default)
Low Battery
LOW.BATT
9
Positive Voltage
Battery On
PWR.FAIL
10
Positive Voltage
Signal Ground
7
AS/400
UPS Available
UPS Available
11/13
Closed
Battery On
Utility Failure
14/16
Closed
Bypass
UPS Offline
17/19
Closed
Low Battery
Low Battery
23/24
Closed
Signal Ground
12/15/18/25
NOTE
Pin numbers separated by a forward slash ( / ) are connected together internally.