background image

044-05243 Rev A

1-1

Chapter 1

Product Description

Introduction

This manual provides information and procedures for installation, operation, and maintenance of the 
OS-1933-E0-003 Multi-Carrier Power Amplifier (MCPA) Outdoor Booster System. 

Scope of Manual

This manual is intended for use by service technicians familiar with similar types of equipment. It contains 
service information required for the equipment described and is current as of the printing date. Changes which 
occur after the printing date may be incorporated by a complete manual revision or alternatively as additions. 
General Description
The outdoor system (OS), shown in Figures 1-1 through 1-4, is a three-way system operating in a 6

0

MHz 

transmit frequency band from 1930 to 199

0

MHz with an instantaneous bandwidth of any 60MHz within the 

operating transmit band and an uplink frequency range of 1850 to 191

0

 MHz. 

The OS has a sturdy aluminum IP55 rated cabinet with front and rear locking hinged doors equipped with 
intrusion alarms. The door latches are 1/4 turn and require a 10 mm hex socket wrench or nut driver to open 
and close. The doors can be secured with a padlock with a 1/2 inch maximum shank diameter. The front and 
rear doors contain removable, washable air filters.
Bolt inserts located on the cabinet side and bottom panels are for mounting the OS to a secure fixed location. 
RF connections are located on the interface bulkhead plate at the bottom rear of the cabinet. External power, 
communications, and alarm cables are routed through access holes located adjacent to the bulkhead. Cabinet 
ground is also located next to the interface bulkhead.
The OS system provides three forms of alarm reporting; Form-C contact closure, ethernet (web page), and 
wireless modem.
Major features of the OS cabinet include the following:

MCPA

The MCPA module, shown in Figure 1-5, is a 1900 MHz RF amplifier. The MCPAs operational features include 
a front panel RF OFF/ON/RESET switch and a multicolored LED indicator to display system status. MCPA 
faults are reported via the status alarm web page.

RF Conditioning Unit (RFCU)

The RF Conditioning Unit (RFCU) shown in Figure 1-6 combines up to four separate BTS feeds; two duplexed 
and two simplexed. The RFCU combines, attenuates, and conditions the RF signals. If a critical system failure 
occurs, the RFCU places the system into bypass mode. The RFCU has two Low Noise Amplifier Units with 
adjustable gain, each located between the output and input duplexer on the RX path and the diversity RX path. 
Performance of the RFCU is monitored and reported via the Ethernet web pages. Faults from the RFCU are 
mapped to Form-C and optional wireless modem alarms.

Up to three MCPAs. (one per sector, up to 160W)

Three RF Conditioning Units (RFCU). 

One Control Module

One power system containing up to four rectifier modules.

Two variable-speed fan assemblies, front and rear doors.

Summary of Contents for OS-1933-E0-003

Page 1: ...044 05243 Rev A June 2008 O U T D O O R B O O S T E R S Y S T E M I N S T A L L A T I O N A N D S E R V I C E M A N U A L OS MCPA OUTDOOR SYSTEM OS 1933 E0 003 Installation and...

Page 2: ...in this document may cause 1 Spurious emissions that violate regulatory requirements 2 The equipment to be automatically removed from service when maximum thresholds are exceeded 3 The equipment to no...

Page 3: ...OS 1933 E3 003 Revision Record 044 05243 Rev A i Revision Record Revision Date of Change Reason for Change Rev A June 2008 Initial Release...

Page 4: ...OS 1933 E3 003 Revision Record ii 044 05243 Rev A This page intentionally left blank...

Page 5: ...tial exists for equipment damage or loss of data NOTE Notes contain helpful suggestions or references to material not covered in the document Safety Any personnel involved in installation operation or...

Page 6: ...Safety OS 1933 E3 003 viii 044 05243 Rev A This page intentionally left blank...

Page 7: ...nstallation Instructions 2 2 AC Power 2 3 RF Cable 2 4 Form C Alarms 2 6 External Alarms EA 2 7 MCPA 2 7 Power system Installation 2 9 RFCU Installation 2 9 Chapter 3 Operation Introduction 3 1 Initia...

Page 8: ...arm Inputs 3 18 Chapter 4 Maintenance Introduction 4 1 Periodic Maintenance 4 1 Cleaning Air Inlets Outlets Filter 4 1 Troubleshooting 4 2 MCPA does not have a solid green LED 4 2 Rectifier Module wit...

Page 9: ...alog Box 3 4 3 4 Internet Protocol TCP IP Properties 3 4 3 5 Setting the IP Address 3 5 3 6 Enable the Connection 3 5 3 7 Rectifier Front Panel 3 8 3 8 MCPA Front Panel 3 9 3 9 Controller Module 3 10...

Page 10: ...ifier Modules 3 6 3 5 Activate TMA Channels 3 6 3 6 Adjust LNA Gain 3 7 3 7 Adjust Tx Gain 3 7 3 8 Adjust VSWR Alarm 3 7 3 9 Activate External Alarm Inputs 3 7 3 10 Status Verification 3 8 3 11 Rectif...

Page 11: ...a secure fixed location RF connections are located on the interface bulkhead plate at the bottom rear of the cabinet External power communications and alarm cables are routed through access holes loca...

Page 12: ...air through a filter mounted in the front panel vents and send heated air out the filter mounted in the rear panel The variable speed fans are dependant on the MCPA power system Controller Module tem...

Page 13: ...dule Display X Form C Fan XX Fault FT front RT frear Minor RFCU Fault 3 Sector 1 3 Critical Bypassx DC Fault 3 Sector 1 3 Critical LNA 1 Fault LNA 2 Fault Sector 1 3 Major 1 Rect Comm Fault Minor Rect...

Page 14: ...nuator Section RFCU_Sector_2 SECTOR_0 RF Interface SECTOR_1 RF Interface SECTOR_2 RF Interface BTS TX3 BTS TX4 BTS TX1 RXm BTS TX2 RXd ANT RXd ANT TX RXm VSWR BTS TX3 BTS TX4 BTS TX1 RXm BTS TX2 RXd A...

Page 15: ...n Figure 1 4 Outdoor System Rear View Door Open Power System MCPAs Controller Module Intrusion Alarm Switch Fan RF Conditioning Unit s Rectifier Modules RF Input and Output Interface Ground Power Alar...

Page 16: ...OS 1933 E3 003 Scope of Manual 1 6 044 05243 Rev A Figure 1 5 MCPA Figure 1 6 RF Conditioning Unit Figure 1 7 Control Module Front Panel Front Rear Rear Front...

Page 17: ...Scope of Manual OS 1933 E3 003 044 05243 Rev A 1 7 Figure 1 8 Power System Rectifier 0 Rectifier 1 Rectifier 2 Rectifier 3...

Page 18: ...OS 1933 E3 003 Scope of Manual 1 8 044 05243 Rev A This page intentionally left blank...

Page 19: ...factory for a return material authorization RMA Refer to Chapter 4 Electrical Service Recommendations The base station AC supply to each OS should have a single phase UL listed AC circuit breaker rate...

Page 20: ...d on the left side facing unit to allow for door swing Recommended minimum clearances for the front of the cabinet is 36 inches and 20 inches for the rear of the cabinet Refer to Tables 2 3 and 2 4 re...

Page 21: ...es Digital volt ohm meter Verify voltage Roto hammer Mounting unistrut or cabinet 10 mm hex socket wrench or nut driver Open door latches Drill bit Mounting unistrut or cabinet Screwdriver slotted 5 m...

Page 22: ...rements detailed in Chapter 5 CAUTION Prior to connecting BTS cables verify booster system power is off NOTE Do not install weatherproofing materials to cables until the booster commissioning is compl...

Page 23: ...allation Instructions OS 1933 E3 003 044 05243 Rev A 2 5 Figure 2 2 Interface Bulkhead RFCU Connections Figure 2 3 Controller Module Installation Ground Studs M8 Studs 3 4 19 mm Control Module Thumbsc...

Page 24: ...structed in Table 2 7 Alarm 1 Minor Any cabinet fan fault intrusion or rectifier communication fault The system requires attention Alarm 2 Major The system performance is degraded Alarm 3 Critical 1 S...

Page 25: ...y empty MCPA or RFCU slots before operation of the OS to prevent overheating and ensure proper system airflow Table 2 8 Form C Alarm Terminal Block Relay Connections and Conditions Relay Continuity Me...

Page 26: ...erify MCPA top and bottom quarter turn fasteners are in unlocked position as shown in Figure 2 5 4 Gently slide MCPA into subrack until seated Turn top and bottom quarter turn fasteners clockwise to s...

Page 27: ...brack may cause the pins on the D Sub connector to become recessed or broken Table 2 11 Rectifier Module Configurations Active sectors Max DC Power Number of Rectifier Modules Required Power System Ca...

Page 28: ...OS 1933 E3 003 Installation Instructions 2 10 044 05243 Rev A This page intentionally left blank...

Page 29: ...led at least one cabinet door must be closed and secured to provide adequate cooling All three OS system slots must be populated with an MCPA Rectifier or a blank panel to provide adequate cooling air...

Page 30: ...display a solid green LED If not a solid green reference the troubleshooting section in Chapter 4 11 The LEDs on the front panel of the controller will illuminate solid green for the enabled and funct...

Page 31: ...Controller Module Connections Figure 3 2 Network Connections Dialog Box Powerwave Product 192 168 255 1 Customer BTS Equipment Site LAN Local LAN Ethernet Laptop 192 168 255 2 Ethernet Typical product...

Page 32: ...OS 1933 E3 003 OS System Configuration 3 4 044 05243 Rev A Figure 3 3 Local Area Connection Properties Dialog Box Figure 3 4 Internet Protocol TCP IP Properties...

Page 33: ...3 Activate Sectors Step Action 1 Select the System Configuration Page See Figure 3 15 2 Using the pull down menus in the Installed section choose YES for the Sectors to be utilized The Sectors are 1 f...

Reviews: